Chapter 12 Description of Parameter SettingsCH2000 Series
123
12-
PT100 Detection Level 1
Factory Setting:5.000
Settings 0.000~10.000V
PT100 Detection Level 2
Factory Setting: 7.000
Settings 0.000~10.000V
Make sure Pr. 06-57 > Pr.06-56.
PT100 Level 1 Frequency Protection
Factory Setting: 0.00
Settings 0.00~600.00 Hz
PT100 operation
(1) Use AVI, AUI or ACI(set to 0-10V) for analog voltage input and select PT100 mode.
(2) Choose one of the analog voltage input type: (a)AVI (Pr.03-00=11), (b) AUI (Pr.03-02=11), or
(c) ACI (Pr.03-01=11 and Pr.03-29=1).
(3) When using ACI as analog voltage input, set Pr.03-01=11 and Pr.03-29=1. Then switch SW2
to 0-10V on the I/O control terminal block.
(4) Set Pr.03-23=23 and AFM2 to constant current output. Switch AFM2 (SW2) to 0-20mA on the
I/O control terminal block and set constant current output to 9mA by setting Pr.03-33=45. The
AFM2 constant output current is 20mA * 45% = 9mA.
(5) Pr.03-33 is for adjusting the constant voltage or constant current of AFM2, the setting range is
0~100.00%.
(6) There are two types of action level for PT100. The diagram of PT protecting action is shown
as below:
Level 2 06-57=
Setting range 0.000 10.000V
Factory setting: 7.000V
: ~
Level 1 06-56=
Setting range: 0.000 10.000V
Factory setting: 5.000V
~
Frequency
Command
When voltage of PT100 reaches level 1,
the frequency command goes back to Pr.06-58.
the drive passed the delay time set at Pr06-59 ,
When voltage of PT100 reaches level 2, the drive activate
protecting action by following the setting of Pr.06-29.
Delay time
Pr.06 59
-
(7) PT100 wiring diagram: