Delta Electronics VFD037CH23A-21 Руководство по эксплуатации онлайн [195/638] 460294

Превью страниц Страница 195 / 638
Delta Electronics VFD185CH23A-21 Руководство по эксплуатации онлайн [195/638] 460299
Chapter 11 Summary of Parameter Settings CH2000 Series
11-14
03-19 ACI Signal Loss
0: Disable
1: Continue operation at the last frequency
2: Decelerate to 0Hz
3: Stop immediately and display ACE
0
03-20 Multi-function Output 1 (AFM1) 0: Output frequency (Hz) 0
03-23 Multi-function Output 2 (AFM2) 1: Frequency command (Hz) 0
2: Motor speed (Hz)
3: Output current (rms)
4: Output voltage
5: DC Bus voltage
6: Power factor
7: Power
8: Output torque
9: AVI
10: ACI
11: AUI
12: Iq current
13: Iq feedback value
14: Id current
15: Id feedback value
16: Vq-axis voltage
17: Vd-axis voltage
18: Torque command
19: PG2 frequency command
20: CANopen analog output
21: RS485 analog output
22: Communication card analog output
23: Constant voltage/current output
03-21 Gain of Analog Output 1 (AFM1)
0~500.0%
100.0
03-22
Analog Output 1 when in REV
Direction (AFM1)
0: Absolute output voltage
1: Reverse output 0V; Positive output 0-10V
2: Reverse output 5-0V; Positive output 5-10V
0
03-24 Gain of Analog Output 2 (AFM2)
0~500.0%
100.0
03-25
Analog Output 2 when in REV
Direction (AFM2)
0: Absolute output voltage
1: Output 0V in REV direction; output 0-10V in FWD
direction
2: Output 5-0V in REV direction; output 5-10V in FWD
direction
0
03-26 Reserved
03-27 AFM2 Output Bias
-100.00~100.00%
0.00
03-28 AVI Selection
0: 0-10V
1: 0-20mA
2: 4-20mA
0
03-29 ACI Selection
0: 4-20mA
1: 0-10V
2: 0-20mA
0
03-30 Status of PLC Output Terminal Monitor the status of PLC output terminals
Read
only
03-31 AFM2 0-20mA Output Selection
0: 0-20mA Output
1: 4-20mA Output
0
03-32 AFM1 DC output setting level 0.00~100.00% 0.00
03-33 AFM2 DC Output Setting Level 0.00~100.00% 0.00
03-34 Reserved

Содержание

1610