Chapter 11 Summary of Parameter SettingsCH2000 Series
11-5
00-26 Max. User Defined Value
0: Disable
0~65535 (when Pr.00-25 set to no decimal place)
0.0~6553.5 (when Pr.00-25 set to 1 decimal place)
0.0~655.35 (when Pr.00-25 set to 2 decimal place)
0.0~65.535 (when Pr.00-25 set to 3 decimal place)
0
00-27 User Defined Value
Read only
Read
Only
00-28
Reserved
00-29 LOCAL/REMOTE Selection
0: Standard HOA function
1: Switching Local/Remote, the drive stops
2: Switching Local/Remote, the drive runs as the
REMOTE setting for frequency and operation
status
3: Switching Local/Remote, the drive runs as the
LOCAL setting for frequency and operation
status
4: Switching Local/Remote, the drive runs as
LOCAL setting when switch to Local and runs as
REMOTE setting when switch to Remote for
frequency and operation status.
0
00-30
Source of the Master Frequency
CommandHAND
0: Digital keypad
1: RS-485 serial communication
2: External analog input (Pr.03-00)
3: External UP/DOWN terminal
4: Pulse input without direction command (Pr.10-16
without direction)
5: Pulse input with direction command (Pr.10-16)
6: CANopen communication card
7: Reserved
8: Communication card (no CANopen card)
0
00-31
Source of the Operation Command
HAND
0: Digital keypad
1: External terminals. Keypad STOP disabled.
2: RS-485 serial communication. Keypad STOP
disabled.
3: CANopen communication card
4: Reserved
5: Communication card (not include CANopen card)
0
00-32 Digital Keypad STOP Function
0: STOP key disable
1: STOP key enable
0
00-33
~
00-39
Reserved
00-40
Homing mode
X
Note: Forward run = clockwise (CW)
Reverse run = counterclockwise (CCW)
0: Forward run to home. Set PL forward limit as
check point.
1: Reverse run (CCW) to home. Set NL reverse
limit (CCWL) as check point.
2: Forward run to home. Set ORG: OFFON
as check point.
3: Reverse to home. Set ORG: OFFON as
check point.
4
Fd
dhfZ
l
hk
0000

Содержание

1610

Изучите основные параметры настройки для управления устройствами, включая выбор источника частоты и команд. Узнайте, как оптимизировать работу с помощью различных режимов.