Chapter 12 Description of Parameter SettingsCH2000 Series
12-13
Reserved
PLC Command Mask
Factory Setting: Read Only
Settings
Bit 0: Control command by PLC force control
Bit 1: Frequency command by PLC force control
Bit 2: Position command by PLC force control
Bit 3: Torque command by PLC force control
This parameter determines if frequency command or control command is occupied by PLC
Source of the Master Frequency CommandAUTO
Factory Setting: 0
Settings
0: Digital keypad
1: RS-485 serial communication
2: External analog input (Pr.03-00)
3: External UP/DOWN terminal
4: Pulse input without direction command (Pr.10-16 without direction)
5: Pulse input with direction command (Pr.10-16)
6: CANopen communication card
7: Reserved
8: Communication card (no CANopen card)
It is used to set the source of the master frequency in AUTO mode.
Pr.00-20 and 00-21 are for the settings of frequency source and operation source in AUTO mode.
Pr.00-30 and 00-31 are for the settings of frequency source and operation source in HAND mode.
The AUTO/HAND mode can be switched by the keypad KPC-CC01 or multi-function input terminal
(MI).
The factory setting of frequency source or operation source is for AUTO mode. It will return to AUTO
mode whenever power on again after power off. If there is multi-function input terminal used to
switch AUTO/HAND mode. The highest priority is the multi-function input terminal. When the
external terminal is OFF, the drive won’t receive any operation signal and can’t execute JOG.
Source of the Operation Command AUTO
Factory Setting: 0
Settings 0: Digital keypad
1: External terminals. Keypad STOP disabled.
2: RS-485 serial communication. Keypad STOP disabled.
3: CANopen card
4: Reserved
5: Communication card (not includes CANopen card)
It is used to set the source of the operation frequency in AUTO mode.
When the operation command is controlled by the keypad KPC-CC01, keys RUN, STOP and JOG
(F1) are valid.