Delta Electronics VFD037CH23A-21 — настройки параметров управления для промышленных устройств [253/638]

Превью страниц Страница 253 / 638
Delta Electronics VFD075CH23A-21 Руководство по эксплуатации онлайн [253/638] 460296
Chapter 12 Description of Parameter SettingsCH2000 Series
12-37
Settings Functions Descriptions
19 Digital Up command
20 Digital Down command
When the contact is ON, the frequency will be increased and
decreased. If this function is constantly ON, the frequency will be
increased/decreased by Pr.02-09/Pr.02-10.
21 PID function disabled When the contact is ON, the PID function is disabled.
22 Clear counter
When the contact is ON, it will clear current counter value and
display “0”. Only when this function is disabled, it will keep counting
upward.
23
Input the counter value
(multi-function input
command 6)
The counter value will increase 1 once the contact is ON. It needs
to be used with Pr.02-19.
24 FWD JOG command
This function is valid when the source of operation command is
external terminals.
When the contact is ON, the drive will execute forward Jog
command.
When execute JOG command under torque mode, the drive will
automatically switch to speed mode; after JOG command is done,
the drive will return to torque mode.
25 REV JOG command
This function is valid when the source of operation command is
external terminals.
When the contact is ON the drive will execute reverse Jog
command.
When execute JOG command under torque mode, the drive will
automatically switch to speed mode; after JOG command is done,
the drive will return to torque mode.
26
FOCPG/TQCPG mode
selection
When the contact is ON: TQCPG mode.
When the contact is OFF: FOCPG mode.
RU N
STOP
ON OFF
OFF ON
RU N/STOP
command
sp eed
command
speed limit speed limit sp eed
command
torque
command
torque
command
torque
limit
torque
limit
sp eed
co ntrol
sp eed
co ntrol
torque
control
torque
control
sp eed
co ntrol
(decel. to stop )
contro l
mode
03 -0 0~ 02= 2
(AVI /AUI/ ACI i s
tor que co mman d)
03 -0 0~02= 1
(AVI/AUI/ACI is
fr eq uen cy co mman d)
Mul t i- f unc ti on i np ut
ter minal is set to 26
(torque/speed
mode switch)
Sw itch timing for t orq ue/speed control
(00-10=0/4 , mu lt i-fu nct ion inpu t t erminal is set to 2 6)
27 ASR1/ASR2 selection
When the contact is ON: speed will be adjusted by ASR 2 setting.
OFF: speed will be adjusted by ASR 1 setting. Refer to Pr.11-02 for
details.
28
Emergency stop (EF1)
When the contact is ON, the drive will execute emergency stop and
display EF1 on the keypad. The motor won’t run and be in the free
run until the fault is cleared after pressing RESET” (EF: External
Fault)

Содержание

1610

Изучите настройки параметров управления, включая команды JOG, функции PID и управление частотой. Оптимизируйте работу вашего оборудования с помощью этих функций.