Chapter 12 Description of Parameter SettingsCH2000 Series
12-52
Multi-function Output Setting
Factory Setting: 0000
Settings
0000h~FFFFh0:N.O. ; 1:N.C.
The setting of this parameter is in hexadecimal.
This parameter is set via bit setting. If a bit is 1, the corresponding output acts in the opposite way.
Example:
If Pr02-13=1 and Pr02-18=0, Relay 1 is ON when the drive runs and is open when the drive is
stopped.
If Pr02-13=1 and Pr02-18=1, Relay 1 is open when the drive runs and is closed when the drive is
stopped.
Bit setting
bit15 bit14 bit13 bit12 bit11 bit10 bit9 bit8 bit7 bit6 bit5 bit4 bit3 bit2 bit1 bit0
MO20 MO19 MO18 MO17 MO16 MO15 MO14 MO13 MO12 MO11 MO10 MO2 MO1 Reserved RY2 RY1
Terminal Counting Value Attained (return to 0)
Factory Setting: 0
Settings 0~65535
The counter trigger can be set by the multi-function terminal MI6 (set Pr.02-06 to 23). Upon
completion of counting, the specified output terminal will be activated (Pr.02-13~02-14, Pr.02-36,
02-37 is set to 18). Pr.02-19 can’t be set to 0.
When the display shows c5555, the drive has counted 5,555 times. If display shows c5555, it
means that real counter value is between 55,550 to 55,559.
Preliminary Counting Value Attained (not return to 0)
Factory Setting: 0
Settings 0~65535
When the counter value counts from 1 and reaches this value, the corresponding multi-function
output terminal will be activated, provided one of Pr. 02-13, 02-14, 02-36, 02-37 set to 17
(Preliminary Count Value Setting). This parameter can be used for the end of the counting to make
the drive runs from the low speed to stop.
1.0msec
TRG
[00-04=01]
02-14=17
02-19=5
02-20=3
[02-06=23]
Display value
Counter Trigger
(output signal)
Preliminary Counter Value
RY1 Pr.02-13 =17
Terminal Counter Value
RY2 Pr.0 2-14 =18
The width of trig ger si gnal
02-13, 02-14, 02-36, 02-37
1.0msec
Digital Output GainDFM
Factory Setting: 1