Chapter 12 Description of Parameter SettingsCH2000 Series
64
12-
Positive torque
Reverse
03-00~02=7
Positive torque limit
03-00~02=8
Negative torque limit
03-00~02=9
Regenerative
torque limit
03-00~02=10
Positive/negative torque limit
Negative Torque
Forward
03-00~02=10
Positive/negative torque limit
03-00~02=9
Regenerative
torque limit
When Pr.03-00~Pr.03-02 have the same setting, then the AVI will be the prioritized selection.
Analog Input Bias (AVI)
Factory Setting: 0
Settings -100.0~100.0%
It is used to set the corresponding AVI voltage of the external analog input 0.
Analog Input Bias (ACI)
Factory Setting: 0
Settings -100.0~100.0%
It is used to set the corresponding ACI voltage of the external analog input 0.
Analog Voltage Input Bias (AUI)
Factory Setting: 0
Settings -100.0~100.0%
It is used to set the corresponding AUI voltage of the external analog input 0.
The relation between external input voltage/current and setting frequency: 0~10V (4-20mA)
corresponds to 0-60Hz.
Reserved
Positive/negative Bias Mode (AVI)
Positive/negative Bias Mode (ACI)
Positive/negative Bias Mode (AUI)
Factory Setting: 0
Settings 0: Zero bias
1: Lower than or equal to bias
2: Greater than or equal toe bias
3: The absolute value of the bias voltage while serving as the center