Chapter 12 Description of Parameter SettingsCH2000 Series
118
12-
When malfunction occurs, please check the drive status (communication address 2119H). If
malfunction happens again, the previous record will be overwritten by this parameter.
Reserved
Reserved
Treatment to Output Phase Loss (OPHL)
Factory Setting: 3
Settings 0: Warn and keep operating
1: Warn and ramp to stop
2: Warn and coast to stop
3: No warning
Pr.06-45 defines how the drive will operates when output phase loss occur.
Deceleration Time of Output Phase Loss
Factory Setting:0.500
Settings 0.000~65.535 sec
Current detection level of output phase loss
Factory Setting:1.00
Settings 0.00~655.35%
Output phase loss detection function executing time before run
Factory Setting:0.000
Settings 0.000~65.535 sec
During the run: Any output phase current is smaller than the level of Pr06-47 and starts to count
time to surpass Pr06-46
Before the run:
01 When performing output phase loss detection, if any output phase is smaller than the level of
Pr06-47 and starts to count time to surpass Pr06-46 that means the motor drive has an output phase
loss and the motor drive will follow the setting of Pr06-45.
02 When Pr06-48 = 0, output phase loss detection before the run is disable.
03 The setting value of Pr06-48 must be larger than the setting of Pr06-46.
Reserved
Reserved
Reserved
Reserved