Delta Electronics VFD037CH23A-21 — настройки параметров для управления двигателем переменного тока [346/638]

Превью страниц Страница 346 / 638
Delta Electronics VFD185CH23A-21 Руководство по эксплуатации онлайн [346/638] 460299
Chapter 12 Description of Parameter SettingsCH2000 Series
12-130
Time
B.B.
output current A
Input B.B. signal
Stop output voltage
Disable B.B. signal
Waiting time 08.07
Speed Search
Synchronization speed detection
Output frequency
(H)
07-09 Current Limit
for Speed Search Speed
FWD Run
B.B. Search with minimum output frequency upward timing chart
Output voltage
(V)
B.B. Search with minimum output frequency upward timing chart
Output frequency(H)
Output voltage(V)
Output current
06-03
Over-Current Stall
Prevention
during Accel.
FWD Run
Time
Input B.B. signal
Stop voltage output
Disable B.B. signal
Waiting time Pr.07-08
Speed search
Synchronization speed detection
B.B.
A
Current Limit for Speed Search
Factory Setting: 50
Settings 20~200%
Following a momentary power loss, the AC motor drive will start its speed search operation only if
the output current is greater than the value set by Pr.07-09.
When executing speed search, the V/f curve is operated by group 1 setting. The maximum current
for the optimum accel./decel. and start speed search is set by Pr.07-09.
The speed search level will affect the synchronous time. It will get the synchronization faster when
this parameter is set to larger value. But too large value may activate overload protection.
Treatment after Fault
Factory Setting: 0
Settings 0: Stop operation
1: Speed search starts with current speed
2: Speed search starts with minimum output frequency
In PG control mode, the AC motor drive will execute the speed search function automatically by
the PG speed when this setting isn’t set to 0.

Содержание

1610

Изучите настройки параметров для оптимизации работы двигателя переменного тока. Узнайте о текущих ограничениях, скорости поиска и обработке ошибок.