Chapter 12 Description of Parameter SettingsCH2000 Series
12-138
Recovery Time to Pr.07-11 (# of automatic reboots after fault)
Factory Setting:60.0
Settings 00~6000.0 sec
When a reset/restart after fault occurs, the drive will regards Pr.07-33 as a time boundary and
begin counting the numbers of faults occur within this time period. Within the period, if numbers of
faults occurred did not exceed the setting in Pr.07-11, the counting will be cleared and starts from
0 when next fault occurs. However, if the numbers of faults occurred within this time period have
exceed the setting in Pr.07-11, user will need to press RESET key manually for the drive to
operate again.