Chapter 12 Description of Parameter SettingsCH2000 Series
12-169
Parameters 10-04 to 10-07 can be used with the multi-function input terminal (set to 48) to switch
to Pr.10-04~10-05 or Pr.10-06~10-07 as shown as follows
ON =A2:B2
OFF=A1:B1
MI=48
Driver
PG
card
Motor
Gear
B1 or B2
Gear
A1 or A2
gear ratio
load
encoder is used
at load side
Treatment for Encoder Feedback Fault
Factory Setting: 2
Settings 0: Warn and keep operating
1: Warn and RAMP to stop
2: Warn and COAST to stop
Detection Time of Encoder Feedback Fault
Factory Setting: 1.0
Settings 0.0~10.0 sec
0: No function
When encoder loss, encoder signal error, pulse signal setting error or signal error, if time exceeds
the detection time for encoder feedback fault (Pr.10-09), the encoder signal error will occur. Refer
to the Pr.10-08 for encoder feedback fault treatment.
Encoder Stall Level
Factory Setting: 115
Settings 0~120%
0: No function
This parameter determines the maximum encoder feedback signal allowed before a fault occurs.
(Max. output frequency Pr.01-00 =100%)
Detection Time of Encoder Stall
Factory Setting: 0.1
Settings 0.0~2.0 sec
Treatment for Encoder Stall
Factory Setting: 2
Settings
0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
When the motor frequency exceeds Pr.10-10 setting and detection time exceeds Pr.10-11, it will
operate as Pr.10-12 setting.