Chapter 12 Description of Parameter SettingsCH2000 Series
12-171
needs 4096 pulses to rotate the motor a revolution.
Assume that Pr.10-01=1024, Pr.10-02=1, Pr.10-16=1, Pr.00-20=5, MI=37 and ON, it needs 1024
pulses to rotate the motor a revolution.
Position control diagram
d
dt
kd
kp
+
-
11-00 bi t 0=0
11-24
11-00 bi t 0=1
11-0
5
11-2510-21
+
+
10-17
10-18
A
B
Position
command
Electrical
gear
Position
feedback
Speed
command
Electrical Gear A
Electrical Gear B
Factory Setting: 100
Settings 1~65535
Rotation speed = pulse frequency/encoder pulse (Pr.10-01) * PG Electrical Gear A / PG Electrical
Gear B.
Positioning for Encoder Position
Factory Setting: 0
Settings 0~65535 pulse
This parameter determines the internal position in the position mode.
It needs to be used with multi-function input terminal setting =35 (enable position control).
When it is set to 0, it is the Z-phase position of encoder.
Range for Encoder Position Attained
Factory Setting: 10
Settings 0~65535 pulse
This parameter determines the range for internal positioning position attained.
For example:
When the position is set by Pr.10-19 Positioning for Encoder Position and Pr.10-20 is set to 1000, it
reaches the position if the position is within 990-1010 after finishing the positioning.
Filter Time (PG2)
Factory Setting: 0.100
Settings 0.000~65.535 sec
When Pr.00-20 is set to 5 and multi-function input terminal is set to 37 (OFF), the pulse command
will be regarded as frequency command. This parameter can be used to suppress the jump of
speed command.