Chapter 16 PLC Function CH2000 Series
16-128
Torque Control:
The corresponding registers for Torque Mode are listed in the chart below:
Special M Control Setting
Special M Description R/W
M1040 Power ON
RW
Special M Status
Special M Description R/W
M1056 Power ON ready
RO
M1063 Target torque attained
RO
Special D Control Setting
Special D Description R/W
D1060 Mode setting (Torque mode=2)
RW
Special D Status
Special D Description R/W
D1050 Actual mode (0:Speed, 1: Position, 2: Torque, 3: Homing)
RO
D1053 Actual torque
RO
Control command for Torque Mode:
TORQ(P)
S1 S2
Target torque (signed decimal) Frequency limit
Example of Torque Control Mode:
Before setting PLC program to torque control mode, maker sure the torque parameter settings of
the AC motor drive are completed.
1. When setting D1060 = 2, AC motor drive is in torque mode.
2. Write TORQ command to PLC program for torque and speed limit control.
3. When setting M1040 = 1, AC motor drive power turns ON and operate till target torque or
speed limit is attained. Actual torque value can be read in D1053.