Daikin RZQS100B7V3B [106/344] Setting the wireless remote controller

Daikin RZQS100B7V3B [106/344] Setting the wireless remote controller
SiBE27-702 Test Operation
Test Operation 93
1.2 Setting the Wireless Remote Controller
Introduction To set the wireless remote controller, you have to set the address for:
The receiver of the wireless remote controller
The wireless remote controller.
Setting the
address for the
receiver
The address for the receiver of the wireless remote controller is factory set to 1. To change this
setting, proceed as follows:
Step Action
1 Turn OFF the power.
2 Remove the sealing pad on the top of the receiver.
3 Set the wireless address switch (SS2) according to the table below. You can find the
wireless address switch attached on the PCB of the receiver and it is visible through the
small opening on the back of the receiver.
4 If you use a wired and a wireless remote controller for one indoor unit, proceed as
follows:
1. Set the wired remote controller to MAIN: On the remote controller.
2. Set the wireless remote controller to SUB: On the receiver with the MAIN/SUB switch
(SS1).
5 Seal off the opening of the address switch and the MAIN/SUB switch with the attached
sealing pad.
6 Make sure to also change the address on the remote controller.