SiBE27-702 Procedure of Self-Diagnosis by Remote Controller
Troubleshooting 159
: Error code displays automatically and system stops.
Inspect and repair it.
: In the case of the shaded error codes, “inspection” is not displayed. The system
operates, but be sure to inspect and repair it.
: Error code displays with blinking.
The system operates, but be sure to inspect and repair it.
Notes: 1. There is a possibility of open phase power supply, check power supply also.
2. Operation when a malfunction occurs may differ according to the model.
3. RZQ100~140C7V1B, RZQS125·140C7V1B
4. RZQ71B9V3B, RZQS71·100B7V3B, RZQ100~140B8W1B
P1 Open phase or voltage unbalance
P4 Abnormal radiation fin temperature sensor
(outdoor unit)
PJ Failure of capacity setting (outdoor unit) Either capacity data is set incorrectly, or capacity
has not been set for the data IC
U0 Lack of gas malfunction Abnormal suction pipe temperature
Applicable Models : (Note 4)
U0 Abnormal suction pipe temperature
Applicable Models : (Note 3)
U0
U2 Abnormal power supply voltage Including malfunction of K1M, K2M
U4/UF Failure of transmission (between indoor and
outdoor unit)
Transmission between indoor and outdoor unit is
not being correctly carried out. (Note 1, Note 2)
UF Failure of transmission (between indoor and
outdoor unit)
or
Piping and wiring mismatch
or
Gas shortage
Transmission between indoor and outdoor unit is
not being correctly carried out.
or
There is very little or no refrigerant flow within the
indoor unit
Applicable Models : (Note 3)
U5 Failure of transmission (between indoor unit and
remote controller)
Transmission between indoor and remote
controller is not being correctly carried out.
U8 Failure of transmission (between “main” and
“sub” remote controller
Transmission between “main” and “sub” remote
controller is not being correctly carried out.
UA Failure of fieldsetting System fieldsetting error pair, twin, triple, double
twin or wrong capacity class.
UC Address error of central remote controller
Malfunction Code Contents/Processing Remarks