Daikin RZQS100B7V3B [85/344] Starting control

Daikin RZQS100B7V3B [85/344] Starting control
Frequency Regulating Functions SiBE27-702
72 Functional Description
4.2 Starting Control
Starting control When compressor start up, the starting frequency is fixed for specified period of time at low
frequency to prevent returning of refrigerant.
RZQ71B9, RZQS71·100 (1 phase), RZQ100~140 (3 phase)
RZQ100~140C7, RZQS125·140 (1 phase)
• RZQ71B9,
RZQS71·100B7:
1φ: 73Hz
• RZQ100B8:
3φ: 107Hz
L
M
OFF
Pressure
equalizing
start
Pressure
equalizing
complete
Starting
control
complete
Pressure equalizing
control before
compressor start
Starting control
Compressor
Electronic
expansion valve
Outdoor unit fan
Indoor unit fan
(Thermostat OFF)
(Remote controller OFF)
480 pls
L (Cooling)
(Heating)
10~120 sec.
OFF
(Cooling Ta>40˚C, Heating Ta<26˚C)
8 Step ON
(Cooling Ta40˚C, Heating Ta>26˚C)
Set fan speed (Cooling)
LL (Heating)
65 pls
15 sec.
112Hz
L
M
OFF
Pressure
equalizing
start
Pressure
equalizing
complete
Starting
control
complete
Pressure equalizing
control before
compressor start
Starting control
Compressor
Electronic
expansion valve
Outdoor unit fan
Indoor unit fan
(Thermostat OFF)
(Remote controller OFF)
Cooling or
Heating(<25˚C)
65 pls
L (Cooling)
(Heating)
10~120 sec.
OFF
(Cooling Ta>40˚C, Heating Ta<26˚C)
8 Step ON
(Cooling Ta40˚C, Heating Ta>26˚C)
Set fan speed (Cooling)
LL (Heating)
Heating(>25˚C)
480 pls