Functional Description 83
4.11 Pressure Difference Control
Outline To ensure the compression ratio (pressure difference between high and low pressure) at low
outdoor temperature conditions in cooling mode and high outdoor temperature conditions in
heating mode, the outdoor fan and target compressor frequency may be varied.
Cooling In cooling low ambient conditions, the outdoor fan speed and compressor frequency will be
adapted to secure the differential pressure between high and low pressure.
Fan control in
cooling
B Series : RZQ71B9, RZQS71·100B7V3B (1 phase), RZQ100~140B8W1B (3 phase)
Parameters
P > 15bar
Compression ratio > 3.2
Normal control
Upper limit (step 8)
Upper limit (step 8)
Upper limit (step 7)
Upper limit (step 6)
Upper limit (step 5)
Upper limit (step4)
Upper limit (step 3)
Upper limit (step 2)
Upper limit (step 1)
Upper limit (step 0)
= Outdoor fan OFF
Condition B
Condition B
Condition B
Condition B
Condition B
Condition B
Condition B
Outdoor fan upper limit : step 8
P > 11bar
Compression ratio > 2.4
Condition B
90 seconds have passed
HP > 20bar (RZQ(S)71: 1
φ
)
HP > 17bar (RZQS100: 1
φ
,
RZQ100~140: 3
φ
)
P > 10bar
Compression
ratio >2.2
&
&
&
&
HP > 30 bar (RZQ(S)71: 1
φ
)
HP > 35 bar (RZQS100: 1
φ
)
HP > 35 bar (RZQ100~140: 3
φ
)
Ta > 27°C
OR
OR
&
&
OR
OR
&
OR
T
Fin
< (T - 15) °C
90 seconds have passed
HP < 16 bar
P < 8bar
Compression ratio < 1.8
90 seconds have passed
HP < 16 bar
P < 8bar
Compression ratio
1.8
Condition A
P < 9.3bar (1
φ
)
P < 9.5bar (3
φ
)
Compression ratio < 2.1
HP < 19 bar
Ta < 25°C
&
OR
HP > 18 bar
Tfin
T °C
P > 9bar
Compression
ratio > 2.0
Condition A
Condition A
Condition A
Condition A
Condition A
Condition A
Condition A
Condition B *1
Condition A *1
*1 RZQ100~140B8W1B (3 phase) only
1 phase 3 phase
RZQ(S)71 RZQS100 RZQ100~140B7W1B
T°C 79°C 71°C 68°C