Daikin RZQS100B7V3B [315/344] Removal of thermistor

Daikin RZQS100B7V3B [315/344] Removal of thermistor
RZQ71B9, RZQS71·100B7V3B / RZQ100~140B8W1B SiBE27-702
302 Removal Procedure
1.8 Removal of Thermistor
Procedure Warning Be sure to commence the disassembling work after 10 minutes or
more elapsed from all power supplies have been turned off.
Step
Procedure Points
Remove the front and top
panels in accordance with
the Removal Procedure
for Outside Panels.
RZQ71B9, RZQS71·100B7V3B
1
In order to remove the
discharge pipe
thermistor, pinch the
mounting spring and
pull out this thermistor.
2
For the heat exchange
thermistor, pull the
clamp frontward and
then remove this
thermistor.
3
In order to remove the
outdoor air thermistor,
pull out this thermistor
frontward and then slide
it to the right.
4
For the suction pipe
thermistor, pull this
thermistor frontward
and then remove it.
Suction pipe thermistor
Mounting
spring
Thermistor
Outdoor air thermistor
Thermistor
Heat exchange thermistor
Clamp
Thermistor
Discharge pipe thermistor
Thermistor