SiBE27-702 Troubleshooting by Remote Controller Display / LED Display
Troubleshooting 187
5.18 E4” Actuation of Low Pressure Sensor: Three phase B
Series
Remote
Controller
Display
E4
Applicable
Models
RZQ100~140B8W1B
Method of
Malfunction
Detection
The protection device circuit checks continuity in the low pressure sensor.
Error generation The error is generated when the low pressure sensor is activated during compressor operation.
Supposed
Causes
The possible causes are:
Malfunctioning refrigerant piping circuit
Malfunctioning low pressure sensor
Disconnected or broken low pressure sensor harness
Malfunctioning low pressure sensor connector connection
Malfunctioning outdoor unit PC board
Stop valve is not opened.
LPS settings The table below contains the preset LPS values.
Refer to P75 for details
Applicable units Abnormal Reset
RZQ100~140 < 1.2 bar > 2 bar