SiBE27-702 Troubleshooting by Remote Controller Display / LED Display
Troubleshooting 195
Is the
resistance value of the fan
motor normal?
NO
YES
Replace the fan motor.
There is no problem with
the unit. An external
factor (noise, etc.) other
than unit failure may be
a cause of the
malfunction.
*1 Fuse conductive
Properly plug the fan motor connector
and then turn ON the power again.
Is the fuse
conductive? (*1)
NO
YES
Dose "E7" appear again?
YES
NO
Replace the fuse.
RZQ71B9,
RZQS71·100B7 (1φ),
RZQ100~140B8 (3φ):
Replace the outdoor
inverter PC board
(A2P).
RZQ100~140C7,
RZQS125·140C7 (1φ):
Replace the outdoor
PC board (A2P).
RZQ100~140C7V1B, RZQS125~140C7V1B
RZQ100~140B8W1B
RZQ71B9V3B, RZQS71~100B7V3B
F6U
F1U (A2P)
No Fuse
A