Daikin RZQS100B7V3B [262/344] Rzq71b9v3b rzqs71 100b7v3b measure the voltage dc between pins 2 and 3 of the connector

Daikin RZQS100B7V3B [262/344] Rzq71b9v3b rzqs71 100b7v3b measure the voltage dc between pins 2 and 3 of the connector
SiBE27-702 Troubleshooting by Remote Controller Display / LED Display
Troubleshooting 249
Outdoor Unit: Check Low Pressure Sensor
RZQ71B9V3B, RZQS71·100B7V3B
Measure the voltage (DC) between pins 2 and 3 of the connector.
Check No.12
Detected Pressure
Output voltage (V
L)
Low Pressure (P
L)
P
L = 0.57V-0.28
P
L: Low pressure (MPa)
V: Voltage (V)
P
L = Detected Presuure (Low side) MPa
V
L: Output voltage (Low side) Vdc
(Blue)
Low pressure sensor
Red
Black
White
+5V
Outdoor unit PC board
Microcomputer
A/D input
Measure voltage (DC) here.
f
e
d
c
(S2680)
(V3053)
P
H, PL
(Kg/cm²) MPa
5.0
4.5
4.0
3.5
3.0
2.5
2.0
1.5
1.0
0.5
0.5 1.5 2.5
-0.5
-0.5 0 1 2 3.534
Vdc
51.0
45.9
40.8
35.7
30.6
25.5
20.4
15.3
10.2
5.1
-5.1
00