Daikin RZQS100B7V3B [124/344] B setting mode 2

Daikin RZQS100B7V3B [124/344] B setting mode 2
SiBE27-702 Field Settings
Test Operation 111
b. “Setting mode 2”
In this mode, settings for the following items can be made by using BS buttons.
The figures in the columns under "No." represent the number of times to push the
SET (BS2) button.
Setting of Demand 2 operation
With this setting, compressor operation can be controlled to reduce power consumption.
(60% - 80% demand is available when a demand adapter (optional accessory) is used.)
[Work procedure]
No.
Display of setting items Display of setting condition
Setting item
LED display
Setting condition
LED display
H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P
3
Demand 2
operation
811118830% demand
40% demand (factory
setting)
50% demand
8111811
8111181
8111118
28
Refrigerant
recovery mode
8188811
OFF (factory setting)
ON
8111118
8111181
Setting item Setting condition Description
Demand 2 operation
30% demand
Operates with 30% of rated
power consumption.
40% demand (factory setting)
Operates with 40% of rated
power consumption.
50% demand
Operates with 50% of rated
power consumption.
1: OFF 9: BLINK 8: ON
Operating procedure
H1P H2P H3P H4P H5P H6P H7P
Push and hold the MODE (BS1) button of "Setting mode 1" for 5 seconds
or more and set to "Setting mode 2."
8111111
Push the SET (BS2) button three times to set the LED display as shown
in the table on the right.
8111188
Push the RETURN (BS3) button once. (Present settings are displayed.) 8111191
Push the SET (BS2) button to set the LED
display as shown in the table on the right.
30% of rated power consumption
8111911
40% of rated power consumption
8111191
50% of rated power consumption
8111119
Push the RETURN (BS3) button once to make a
decision.
30% of rated power consumption
8111811
40% of rated power consumption
8111181
50% of rated power consumption
8111118
Push the RETURN (BS3) button once again for execution. (The LED
display is in the initial status of "Setting mode 2".)
8111111
Push the MODE (BS1) button once to return to Setting mode 1 (normal
operation).
1111111
Push and hold the MODE (BS1) button
for 5 seconds and set to “Setting mode
2”.
Push the SET (BS2) button and set the
LED display to a setting item shown in
the table on the right.
Push the RETURN (BS3) button and
decide the item. (The present setting
condition is blinked.)
<Selection of setting items>
<Selection of setting conditions>
Push the SET (BS2) button and set to
the setting condition you want.
Push the RETURN (BS3) button and
decide the condition.
Push the RETURN (BS3) button and
set to the initial status of “Setting mode
2”.
If you become unsure of how to proceed,
push the MODE (BS1) button and return
to setting mode 1.