Chapter 12 Description of Parameter SettingsCH2000 Series
12-40
Settings Functions Descriptions
(valid at stop)
positions and write current motor position into such corresponding
multi-step position.
MI=d1
Run/Stop
1
1
1010 =10
2
corresponds to
Pr.04-34
11
0
0
0
00
11 1
1011 =11
2
corresponds
to Pr.04-36
MI=d2
MI=d3
MI=d4
MI=d36
Writing the motor position
into the Pr.04-3
6
Writing the motor position
into the Pr.04-34
37
Full position control
pulse command input
enable
When Pr.00-20 is set to 4 or 5 and this contact is ON, the input
pulse of PG card is position command. When using this function, it
is recommended to set Pr.11-25 to 0.
Example: please refer to the following diagram when using this
faction with MI=d35 return to home position,.
RUN
MI=d35
MO=d39
MI=d37
pulse
command
internal
positioning
output
frequency
Time
38
Disable EEPROM write
function
(Parameters written
disable)
When this contact is ON, write to EEPROM is disabled. (Changed
parameters will not be saved after power off)
39
Torque command
direction
For torque control (Pr.00-10=2), when torque command is AVI or
ACI, the contact is ON and it is negative torque.
40
Force coast to stop
When this contact is ON during the operation, the drive will free run
to stop.