Chapter 12 Description of Parameter SettingsCH2000 Series
12-41
Settings Functions Descriptions
41
HAND switch
42
AUTO switch
1. When MI is switched to off status, it executes a STOP
command. , If MI is switched to off during operation, the drive
will also stop.
2. Using keypad KPC-CC01 to switch between HAND/AUTO,
the drive will stop first then switch to the HAND or AUTO status.
3. On the digital keypad KPC-CC01, it will display current drive
status (HAND/OFF/AUTO).
Bit 1 Bit 0
OFF 0 0
AUTO 0 1
HAND 1 0
OFF 1 1
43
Enable resolution
selection
Refer to Pr.02-48 for details.
44
Reverse direction
NLhoming
Signal input for reverse direction limit switch. When this terminal is
ON, the drive will react to the setting in Pr.00-40, 00-41, 00-42
accordingly to execute homing in a reverse direction (counter
clockwise).
Note: NL means input terminal detection is negative-edge triggered
or be regarded as NO(Normal Open)
45
Forward direction PL
homing
Signal input for forward direction limit switch. When this terminal is
ON, the drive will react to the setting in Pr.00-40, 00-41, 00-42
accordingly to execute homing in a forward direction (clockwise).
Note: PL means input terminal detection is positive-edge triggered
or be regarded as NC(Normal Close)
46
Homing ORG
ORG point input. When this terminal is ON, the drive will refer to the
setting in Pr.00-40, 00-41, 00-42 accordingly to execute homing.
47
Homing function enable
Pr.00-10 = 3 (homing mode), if the external terminal MIx=47 is
OFF, the drive will ignore the home command and execute Point to
Point position control.
48
Mechanical gear ratio
switch
When this contact is ON, the mechanical gear ratio switch will be
the second group A2/B2 (refer to Pr.10-08 and Pr.10-09).
49 Drive enable
When drive=enable, RUN command is valid.
When drive= disable, RUN command is invalid.
When drive is in operation, motor coast to stop.
This function will interact with MO=51
50 Master dEb action input
Input the message setting in this parameter when dEb occurs to
Master. This will ensure dEb also occurs to Slave, then Master and
Slave will stop simultaneously.
51
Selection for PLC mode
bit0
52
Selection for PLC mode
bit1
PLC status Bit 1 Bit 0
Disable PLC function (PLC 0) 0 0
Trigger PLC to operation (PLC 1) 0 1
Trigger PLC to stop (PLC 2) 1 0
No function 1 1
53
Enable CANopen quick
stop
When this function is enabled under CANopen control, it will
change to quick stop. Refer to Chapter 15 for more details.
54 Reserved
55 Brake Release
#MI=55 needs to be used with Pr02-56. After setting the value
(time) of Pr02-56, if there is no signal input, motor drive will show
error Brk, and mechanical brake will be enabled immediately.
#The default setting of Pr02-56 is 0. If the value is not 0, the brake
signal checking will be activated. If there is no signal input after