Chapter 12 Description of Parameter SettingsCH2000 Series
12-42
Settings Functions Descriptions
time setting (Pr02-56), motor drive will show Brk error, no matter if
there is any other setting about brake control
Run command
Output Freq.
(output Freq.>=Pr02-34 and
output current>=Pr02-33)
Pr02 32-
MI=55
Mechanical delay time
Pr02 56
-
if there is no brake release signal
56
LOCAL/REMOTE Selection
Use Pr.00-29 to select for LOCAL/REMOTE mode(refer to
Pr.00-29)
When Pr.00-29 is not set to 0, on the digital keypad KPC-CC01 it
will display LOC/REM status. (It will display on the KPC-CC01 if the
firmware version is above version 1.021).
Bit 0
REM 0
LOC 1
57~70 Reserved
UP/DOWN Key Mode
Factory Setting: 0
Settings 0: Up/down by the accel/decel time
1: Up/down constant speed (Pr.02-10)
Constant speed. The Accel. /Decel. Speed of the UP/DOWN Key
Factory Setting: 0.01
Settings 0.01~1.00Hz/ms
These settings are used when multi-function input terminals are set to 19/20. Refer to Pr.02-09 and
02-10 for the frequency up/down command.
Pr.02-09 set to 0: it will increase/decrease frequency command (F) by the external terminal
UP/DOWN key as shown in the following diagram. In this mode, it also can be controlled by
UP/DOWN key on the digital keypad.
OFF
ON
Time
Frequency
Frequency command
External terminal
UP key
DCM
DOWN
UP
VFD-C
Ml1~15
Ml1~15