Chapter 12 Description of Parameter SettingsCH2000 Series
12-46
Settings Functions Descriptions
Attained 2 (Pr.02-24)
5
Zero Speed (frequency
command)
A
ctive when frequency command =0. (the drive should be at RUN
mode)
6
Zero Speed with Stop
(frequency command)
Active when frequency command =0 or stop.
7 Over Torque 1
Active when detecting over-torque. Refer to Pr.06-07 (over-torque
detection level-OT1) and Pr.06-08 (over-torque detection
time-OT1). Refer to Pr.06-06~06-08.
8 Over Torque 2
Active when detecting over-torque. Refer to Pr.06-10 (over-torque
detection level-OT2) and Pr.06-11 (over-torque detection
time-OT2). Refer to Pr.06-09~06-11.
9 Drive Ready Active when the drive is ON and no abnormality detected.
10 Low voltage warn (Lv)
Active when the DC Bus voltage is too low. (refer to Pr.06-00 low
voltage level)
11 Malfunction Indication Active when fault occurs (except Lv stop).
12
Mechanical Brake
Release (Pr.02-32)
When drive runs after Pr.02-32, it will be ON. This function should
be used with DC brake and it is recommended to use
contact ”b”(N.C).
13 Overheat
A
ctive when IGBT or heat sink overheats to prevent OH turn off
the drive. (refer to Pr.06-15)
14
Software Brake Signal
Indication
Active when the soft brake function is ON. (refer to Pr.07-00)
15 PID Feedback Error Active when the feedback signal is abnormal.
16 Slip Error (oSL) Active when the slip error is detected.
17
Terminal Count Value
Attained (Pr.02-20; not
return to 0)
A
ctive when the counter reaches Terminal Counter Value
(Pr.02-19). This contact won’t active when Pr.02-20>Pr.02-19.
18
Preliminary Counter
Value Attained
(Pr.02-19; returns to 0)
A
ctive when the counter reaches Preliminary Counter Value
(Pr.02-19).
19
External Base Block
input (B.B.)
Active when the output of the AC motor drive is shut off during
base block.
20 Warning Output Active when the warning is detected.
21 Over-voltage Warning Active when the over-voltage is detected.
22
Over-current Stall
Prevention Warning
Active when the over-current stall prevention is detected.
23
Over-voltage Stall
prevention Warning
Active when the over-voltage stall prevention is detected.
24
Operation Mode
Indication
A
ctive when the operation command is controlled by external
terminal. (Pr.00-200)
25 Forward Command Active when the operation direction is forward.
26 Reverse Command Active when the operation direction is reverse.
27
Output when Current >=
Pr.02-33
Active when current is >= Pr.02-33.
28
Output when Current <=
Pr.02-33
Active when current is <= Pr.02-33
29
Output when frequency
>= Pr.02-34
Active when frequency is >= Pr.02-34.
30
Output when Frequency
<= Pr.02-34
Active when frequency is <= Pr.02-34.
31
Y-connection for the
Motor Coil
Active when PR.05-24 is less than Pr.05-23 and time is more than
Pr.05-25.
32
-connection for the
Motor Coil
Active when PR.05-24 is higher than Pr.05-23 and time is more
than Pr.05-25.
33
Zero Speed (actual
output frequency)
A
ctive when the actual output frequency is 0. (the drive should be
at RUN mode)
34
Zero Speed with Stop
(actual output frequency)
Active when the actual output frequency is 0 or Stop.
35 Error Output Selection 1 Active when Pr.06-23 is ON.