Chapter 12 Description of Parameter SettingsCH2000 Series
107
12-
will decrease its output frequency (according to Pr.06-05) to prevent the motor stall. If the output
current is lower than the setting specified in Pr.06-04, the drive will accelerate (according to
Pr.06-05) again to catch up with the set frequency command value.
Over-Current
Detection Level
06-04
Output
Frequency
Over-Current Stall Prevention
during Operation, output
frequency decreases
over-current stall prevention during operation
Time
Current
Pr. 06-04 setting
Pr. 06-04 setting-
rated dr ive c urrent X 5%
Decreases by
deceleration time
Accel./Decel. Time Selection of Stall Prevention at Constant Speed
Factory Setting: 0
Settings 0: by current accel/decel time
1: by the 1st accel/decel time
2: by the 2nd accel/decel time
3: by the 3rd accel/decel time
4: by the 4th accel/decel time
5: by auto accel/decel
It is used to set the accel./decel. time selection when stall prevention occurs at constant speed.
Over-torque Detection Selection (OT1)
Factory Setting: 0
Settings 0: Disable
1: Over-torque detection during constant speed operation, continue to
operate after detection
2: Over-torque detection during constant speed operation, stop operation
after detection
3: Over-torque detection during operation, continue to operate after detection
4: Over-torque detection during operation, stop operation after detection
Over-torque Detection Selection (OT2)
Factory Setting: 0
Settings 0: Disable
1: Over-torque detection during constant speed operation, continue to
operate after detection
2: Over-torque detection during constant speed operation, stop operation
after detection