Chapter 12 Description of Parameter SettingsCH2000 Series
108
12-
3: Over-torque detection during operation, continue to operation after
detection
4: Over-torque detection during operation, stop operation after detection
When Pr.06-06 and Pr.06-09 are set to 1 or 3, it will display a warning message and won’t have an
abnormal record.
When Pr.06-06 and Pr.06-09 are set to 2 or 4, it will display a warning message and will have an
abnormal record.
Over-torque Detection Level (OT1)
Factory Setting: 120
Settings 10 to 250% (100%: drive’s rated current)
Over-torque Detection Level (OT1)
Factory Setting: 0.1
Settings 0.0~60.0 sec
Over-torque Detection Level (OT2)
Factory Setting: 120
Settings 10 to 250% (100%: drive’s rated current)
Over-torque Detection Time (OT2)
Factory Setting: 0.1
Settings 0.0~60.0 sec
NOTE 01: Over torque detection is determined by the following method.
if the output current exceeds the over-torque detection level (Pr06-07, factory setting: 150%)
and also exceeds Pr06-08, the Over Torque Detection will follow the setting of Pr06-06 and
Pr06-09.
NOTE02: When Pr06-06 or Pr06-09 is set to 1 or 3, the motor drive will have the ot1/ot2 warning
after Over Torque Detection. But the motor drive will keep running but only until the output current
is smaller than the 5% of the rated current, the warning will be off.
5%
Current
06-07, 06-10
06-08, 06-11
ON ON
5%
Output Current
Over Torque
Warning
NOTE03: When Pr06-06 or Pr06-09 is set to 2 or 4, the motor drive will have the ot1/ot2 fault after Over
Torque Detection.
Then the motor drive stop running until it is manually reset.
Current Limit
Factory Setting: 170
Settings 0~250% (100%: drive’s rated current)
Pr.06-12 sets the maximum output current of the drive. Pr.06-12 and Pr.11-17 ~ Pr.11-20 are used