Yaskawa CIMR-PU2A0081 [114/548] Switching between local and remote
n
Setup Group Parameters
Table
4.6 lists the parameters available by default
in the Setup Group. Selecting an Application Preset in through initialization
in parameter A1-03 automatically changes the parameters selected for the Setup Group. Refer to Application Selection on
page 118 for details on parameters and default values for the fan and pump Setup Groups.
No. Parameter Name Setting Range Default
A1-03 Initialize Parameters
0, 1110, 2220, 3330, 5550,
8008, 8009, 8010, 8011
0
Setting 0: No initialization (default)
Setting 1110: User Initialize (parameter values must be stored using parameter o2-03)
Setting 2220: 2-Wire Initialize
Setting 3330: 3-Wire Initialize
Setting 5550: Terminal/Control Initialize
Setting 8008: Pump
Setting 8009: Pump w/ PI
Setting 8010: Fan
Setting 8011: Fan w/ PI
Use the Programming Mode to access parameters not displayed in the Setup Group.
Table 4.6 General Purpose Application Setup Group Parameters (A1-03 = 0)
Parameter Name
A1-06 Application Preset Selection (Monitor only)
b1-01 Frequency Reference Selection 1
b1-02 Run Command Selection 1
b1-03 Stopping Method Selection
b1-04 Reverse Operation Selection
C1-01 Acceleration Time 1
C1-02 Deceleration Time 1
d1-01 Frequency Reference 1
d2-01 Frequency Reference Upper Limit
d2-02 Frequency Reference Lower Limit
Parameter Name
E2-01 Motor Rated Current
L2-01 Momentary Power Loss Operation Selection
L5-01 Number of Auto Restart Attempts
L6-01 Torque Detection 1 Selection
L6-02 Torque Detection 1 Level
L6-03 Torque Detection 1 Time
o1-06 User Monitor Selection Mode
o1-07 Second Line Monitor Selection
o1-08 Third Line Monitor Selection
u
Switching Between LOCAL and REMOTE
LOCAL mode is when the drive is set to accept the Run command from the digital operator RUN key. REMOTE mode is
when the drive is set to accept the Run command from an external device (i.e., input terminals or serial communications).
WARNING! Sudden Movement Hazard. The drive may start unexpectedly if the Run command is already applied when switching from
LOCAL
mode to REMOTE mode when b1-07 = 1, resulting in death or serious injury. Be sure all personnel are clear of rotating machinery.
Switch the operation between LOCAL and REMOTE using the LO/RE key on the digital operator or via a digital input.
Note: 1. After selecting LOCAL, the LO/RE light will remain lit.
2. The drive will not allow the user to switch between LOCAL and REMOTE during run.
n
Using the LO/RE Key on the Digital Operator
Step Display/Result
1. Turn on the power to the drive. The initial display appears.
- MODE -
U1-01= 0.00Hz
U1-02= 0.00Hz
U1-03= 0.00A
DRV
FREF (A1/A2)
Rdy
JOG FWD FWD/REV
RSEQ
RREF
2.
Press
. The LO/RE light will light up. The drive is now in LOCAL.
To set the drive for REMOTE operation, press the key again.
LO
RE
F2F1
ESC
RUN
STOP
ENTERRESET
ALM
DIGITAL OPERATOR JVOP-180
- MODE -
U1-01= 0.00Hz
U1-02= 0.00Hz
U1-03= 0.00A
DRV
FREF (OPR)
Rdy
JOG FWD FWD/REV
LSEQ
LREF
4.3 The Drive, Programming, and Clock Adjustment Modes
114
YASKAWA SIEP YAIP1U 01A AC Drive - P1000 Technical Manual