Yaskawa CIMR-PU2A0081 — подключение выходного сигнала и выбор входного сигнала [93/548]

Превью страниц Страница 93 / 548
Yaskawa CIMR-PU2A0211 [93/548] Using external power supply sink mode
MP
AC
V
MP
R
L
Load Impedance
Figure 3.32 Pulse Output Connection Using Internal Voltage Supply
n
Using External Power Supply (Sink Mode)
The high voltage level of the pulse output signal depends on the external voltage applied. The voltage must be between 12
and 15 Vdc. The load resistance must be adjusted so that the current is lower than 16 mA.
External Power Supply (V) Load Impedance (kΩ)
12 to 15 Vdc ±10% 1.0 kΩ or higher
MP
AC
Load Impedance
Sink Current
External Power Supply
Figure 3.33 Pulse Output Connection Using External Voltage Supply
u
Terminals A1, A2, and A3 Input Signal Selection
Terminals A1, A2, and A3 can be used to input either a voltage or a current signal. Select the signal type using jumper S1 as
explained in Table 3.12. Set parameters H3-01, H3-05, and H3-09 accordingly as shown in Table 3.13. Refer to Switches
and Jumpers on the Terminal Board on page 91 for locating jumper S1.
Note: If terminals A1 and A2 are both set for frequency bias (H3-02 = 0 and H3-10 = 0), both input values will be combined to create the frequency
reference.
V
I
A1 A2 A3
Jumper S1
Figure 3.34 Terminal A2 Set to Current Input; A1 and A3 Set to Voltage Input
Table 3.12 Jumper S1 Settings
Setting Description
V (top position) Voltage input (-10 to +10 V or 0 to 10 V)
I (bottom position) Current input (4 to 20 mA or 0 to 20 mA)
3.10 Control I/O Connections
YASKAWA SIEP YAIP1U 01A AC Drive - P1000 Technical Manual
93
3
Electrical Installation
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com