S3: Secondary PI (PI2) Control
No.
(Addr.
Hex)
Name Description Values Page
S3-01
(321A)
Secondary PI Enable
Selection
PI2 Enable Sel
Determines when the secondary PI controller is enabled.
0: Disabled
0: Disabled
1: Always
1: Always
2: Drive running
2: Drive running
3: Motor running
3: Motor running
Note: Setting 3 does not run the motor
at zero speed, baseblock, or in
DC injection.
Default: 0
Range: 0 to 3
268
S3-02
(321B)
Secondary PI User Display
PI2 UsrDspMaxVal
Sets the scale value of 100% PI input.
Default: 10000
Min.: 0
Max.: 60000
268
S3-03
(321C)
Secondary PI Display Digits
PI2 UsrDspDigits
Sets the decimal place display for secondary PI units.
0: No decimal places
0: No Dec (XXXXX)
1: One decimal place
1: 1 Dec (XXXX.X)
2: Two decimal places
2. 2 Dec (XXX.XX)
3: Three decimal places
3: 3 Dec (XX.XXX)
Default: 2
Range: 0 to 3
269
S3-04
(321D)
Secondary PI Unit
Selection
PI2 Unit Sel
Sets the units for the secondary PI control function.
0: Inch of water (WC)
0: WC
1: Pounds per square inch (PSI)
1: PSI
2: Gallons per minute (GPM)
2: GPM
3: Degrees Fahrenheit (F)
3: °F
4: Cubic feet per minute (CFM)
4: CFM
5: Cubic meters per hour (CMH)
5: CMH
6: Liters per hour (LPH)
6: LPH
7: Liters per second (LPS)
7: LPS
8: Bar (Bar)
8: Bar
9: Pascals (Pa)
9: Pa
10: Degrees Celsius (C)
10: °C
11: Meters (Mtr) (Ft: Feet)
11: Mtr
12: Liters per minute (LPM)
12: LPM
13: Cubic meters per minute (CMM)
13: CMM
14: No unit
14: No unit
15: Percentage (%)
15: %
Default: 15
Range: 0 to 15
269
S3-05
(321E)
Secondary PI Setpoint Value
PI2 Setpoint
Sets the secondary PI controller target value.
Default: 0.00
<1>
Min.: 0.00
Max.: 600.00
<2>
269
S3-06
(321F)
Secondary PI Proportional
Gain Setting
PI2 Gain
Sets the proportional gain of the secondary PI controller. A setting of 0.00
disables P control.
Default: 1.00
Min.: 0.00
Max.: 25.00
269
S3-07
(3220)
Secondary PI Integral Time
Setting
PI2 I Time
Sets the integral time for the secondary PI controller. A setting of 0.0 s disables
integral control.
Default: 1.0 s
Min.: 0.0
Max.: 360.0
269
S3-08
(3221)
Secondary PI Integral Limit
Setting
PI2 I Limit
Sets the maximum output possible from the integrator.
Default: 100.0%
Min.: 0.0
Max.: 100.0
270
S3-09
(3222)
Secondary PI Output Upper
Limit
PI2 Upper Limit
Sets the maximum output possible from the secondary PI controller.
Default: 100.0%
Min.: 0.0
Max.: 100.0
270
S3-10
(3223)
Secondary PI Output Lower
Limit
PI2 Lower Lim
Sets the minimum output possible from the secondary PI controller.
Default: 0.00%
Min.: -100.00
Max.: 100.00
270
S3-11
(3224)
Secondary PI Output Level
Selection
PI2 Out Lvl Sel
Sets the secondary PI controller output direction.
0: Normal Output
0: Normal Character
(direct acting)
1: Reverse Output
1: Rev Character
(reverse acting)
Default: 0
Range: 0, 1
270
B.11 S: Special Application
434
YASKAWA SIEP YAIP1U 01A AC Drive - P1000 Technical Manual