Yaskawa CIMR-PU2A0081 — многофункциональные аналоговые и цифровые входы и выходы [87/548]

Превью страниц Страница 87 / 548
Yaskawa CIMR-PU2A0021 [87/548] Phone 800 94 412 fax 888 23 773 web www clrwtr com email info clrwtr com
Type No. Terminal Name (Function) Function (Signal Level) Default Setting Page
Analog Inputs /
Pulse Train
Input
RP
Multi-function pulse train input
(Frequency reference)
Input frequency range: 0 to 32 kHz
Signal Duty Cycle: 30 to 70%
High level: 3.5 to 13.2 Vdc, low level: 0.0 to 0.8 Vdc
Input impedance: 3 kΩ
140
223
+V Power supply for analog inputs 10.5 Vdc (max allowable current 20 mA) 139
24 V
+24 Vdc transducer power supply for customer
use
150 mA maximum capacity
A1
Multi-function analog input 1
(Frequency reference bias)
-10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 k
Ω)
4 to 20 mA, 0 to 20 mA (input impedance: 250 Ω)
Voltage or current input must be selected by jumper S1 and H3-01.
139
216
A2
Multi-function analog input 2
(Frequency reference bias)
-10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 kΩ)
4 to 20 mA, 0 to 20 mA (input impedance: 250 Ω)
Voltage or current input must be selected by jumper S1 and H3-09.
139
139
218
A3
Multi-function analog input 3
(Frequency reference bias)
-10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 kΩ)
4 to 20 mA, 0 to 20 mA (input impedance: 250 Ω)
Voltage or current input must be selected by jumper S1 and H3-05.
139
AC Frequency reference common 0 V 139
E (G) Ground for shielded lines and option cards
n
Output Terminals
Table
3.7 lists the output terminals on
the drive. Text in parenthesis indicates the default setting for each multi-function output.
Table 3.7 Control Circuit Output Terminals
Type No. Terminal Name (Function) Function (Signal Level) Default Setting Page
Fault Relay
Output
MA N.O.
30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A
Minimum load: 5 Vdc, 10 mA
206MB N.C. output
MC Fault output common
Multi-Function
Digital Output
<1>
MD N.O.
30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A
Minimum load: 5 Vdc, 10 mA
206
ME N.C. Output
MF Common (Speed agree)
M1
Multi-function digital output (During run)
30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A
Minimum load: 5 Vdc, 10 mA
M2
M3
Multi-function digital output (Zero speed)
M4
Monitor
Output
FM Analog monitor output 1 (Output frequency)
-10 to +10 Vdc, or 0 to +10 Vdc 221
AM Analog monitor output 2 (Output current)
AC Monitor common 0 V
<1> Refrain from assigning functions to digital relay
outputs that involve frequent switching, as doing so may shorten relay performance life. Switching
life is estimated at 200,000 times (assumes 1 A, resistive load).
Connect a suppression diode as shown in Figure 3.25 when driving a reactive load such as a relay coil. Ensure the diode rating
is greater than the circuit voltage.
A
B
C
D
A External power, 48 V max.
B Suppression diode
C Coil
D 50 mA or less
Figure 3.25 Connecting a Suppression Diode
3.9 Control Circuit Wiring
YASKAWA SIEP YAIP1U 01A AC Drive - P1000 Technical Manual
87
3
Electrical Installation
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Содержание

2656

Изучите многофункциональные аналоговые и цифровые входы и выходы, их настройки и характеристики. Узнайте о подключении и использовании различных сигналов.