Yaskawa CIMR-PU2A0081 [242/548] L protection functions
Set H2-01, H2-02, or H2-03 to C for a digital output to trigger when frequency reference loss occurs. Refer to Setting C:
Frequency Reference Loss on page 210 for details on setting the output function.
Parameter L4-05 selects the operation when a frequency reference loss is detected.
No. Name Setting Range Default
L4-05 Frequency Reference Loss Detection Selection 0, 1 0
Setting 0: Stop
Drive follows the frequency reference (which is no longer present) and stops the motor.
Setting 1: Continue operation with reduced frequency reference
The drive will continue operation at the frequency reference value set to parameter L4-06. When the external frequency
reference value is restored, the operation is continued with the frequency reference.
n
L4-06: Frequency Reference at Reference Loss
Sets the frequency reference level at which the drive runs when L4-05 = 1 and when detecting a reference loss. The value is
set as a percentage of the frequency reference before the loss was detected.
No. Name Setting Range Default
L4-06 Frequency Reference at Reference Loss 0.0 to 100.0% 80.0%
n
L4-07: Speed Agreement Detection Selection
Determines when frequency detection is active using parameters L4-01 through L4-04.
No. Name Setting Range Default
L4-07 Speed Agreement Detection Selection 0, 1 0
Setting 0: No Detection during Baseblock
Setting 1: Detection always Enabled
u
L5: Fault Restart
After a fault has occurred, Fault Restart attempts to automatically restart the motor and continue operation instead of stopping.
The drive can perform a self-diagnostic check and resume the operation after a fault has occurred. If the self-check is successful
and the cause of the fault has disappeared, the drive restarts by first performing Speed Search (Refer to b3: Speed Search on
page 145 for details).
Note: 1. The wiring sequence should remove the Forward/Reverse command when a fault is triggered and output is shut off.
2. When the Forward/Reverse command is removed, the drive can perform a self-diagnostic check and attempt to restart the fault
automatically.
WARNING! Sudden Movement Hazard. Do not use the fault restart function in lifting applications. Fault restart may cause the machine to
drop the load, which could result in death or serious injury.
The drive can attempt to restart itself following the faults listed below.
Fault Name Fault Name
GF Ground Fault oL4 Overtorque 2
LF Output Open Phase ov DC Bus Overvoltage
oC Overcurrent PF Input Phase Loss
oH1 Drive Overheat rH Braking Resistor Fault
oL1 Motor Overload rr Braking Transistor Fault
oL2 Drive Overload Uv1
DC Bus Undervoltage
<1>
oL3 Overtorque 1
<1> When L2-01 is set to 1 through 4 (continue operation during momentary power loss)
Use parameters L5-01 to L5-05 to set up automatic fault restart.
Set H2-01, H2-02, or H2-03 to 1E. to output a signal during fault restart.
5.8 L: Protection Functions
242
YASKAWA SIEP YAIP1U 01A AC Drive - P1000 Technical Manual