Yaskawa CIMR-PU2A0081 [260/548] The drive keeps the previously saved record concerning fault trace and fault history
n
o4-03: Cooling Fan Operation Time Setting
Sets
the value for how long the
cooling fan has been operating. This value can be viewed in monitor U4-03. Parameter o4-03
also sets the base value used for the cooling fan maintenance, which is displayed in U4-04. Reset this parameter to 0 after
replacing the cooling fan.
Note: 1. The value in o4-03 increases after every 10 hours of use. A setting of 30 will set the cooling fan operation time counter to 300 h. “300”
will be displayed in monitor U4-03.
2. The cooling fan may require maintenance at an earlier date in harsher environments.
No. Name Setting Range Default
o4-03 Cooling Fan Operation Time Setting 0 to 9999 0
n
o4-05: Capacitor Maintenance Setting
Sets value of the maintenance monitor for the DC bus capacitors displayed in U4-05 as a percentage of the total expected
performance life. Reset this value to 0 after replacing the DC bus capacitors.
Note: The actual maintenance time will depend on the environment where the drive is used.
No. Name Setting Range Default
o4-05 Capacitor Maintenance Setting 0 to 150% 0%
n
o4-07: DC Bus Pre-Charge Relay Maintenance Setting
Sets the value of the softcharge bypass relay maintenance time displayed in U4-06 as a percentage of the total expected
performance life. Reset this value to 0 after replacing the bypass relay.
Note: The actual maintenance time will depend on the environment where the drive is used.
No. Name Setting Range Default
o4-07 DC Bus Pre-charge Relay Maintenance Setting 0 to 150% 0%
n
o4-09: IGBT Maintenance Setting
Sets
the value of the IGBT maintenance
time displayed in U4-07 as a percentage of the total expected performance life. Reset
this value to 0 after replacing the IGBTs.
Note: The actual maintenance time will depend on the environment where the drive is used.
No. Name Setting Range Default
o4-09 IGBT Maintenance Setting 0 to 150% 0%
n
o4-11: U2, U3 Initialization
Resets the fault trace and fault history
monitors (U2-oo and U3-oo). Initializing the drive using A1-03 does not reset these
monitors.
No. Name Setting Range Default
o4-11 U2, U3 Initialization 0, 1 0
Setting 0: No Action
The drive keeps the previously saved record concerning fault trace and fault history.
Setting 1: Reset Fault Data
Resets the data for the U2-oo and U3-oo monitors. Setting o4-11 to 1 and pressing the ENTER key erases fault data and
returns the display to 0.
n
o4-12: kWh Monitor Initialization
Resets the kWh monitors U4-10 and U4-11. Initializing the drive or cycling the power does not reset these monitors.
No. Name Setting Range Default
o4-12 kWh Monitor Initialization 0, 1 0
Setting 0: No Action
The kWh data are maintained.
5.10 o: Operator Related Settings
260
YASKAWA SIEP YAIP1U 01A AC Drive - P1000 Technical Manual