H3: Multi-Function Analog Inputs
No.
(Addr.
Hex)
Name Description Values Page
H3-01
(410)
Terminal A1 Signal Level
Selection
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20 mA
3: 0 to 20 mA
Note: Use Jumper S1 to set input terminal
A1 for a current or voltage
input signal.
Default: 0
Range: 0 to 3
216
H3-02
(434)
Terminal A1 Function
Selection
Sets the function of terminal A1. Default: 0
Range: 0 to 32
216
H3-03
(411)
Terminal A1 Gain Setting
Sets the level of the input value selected in H3-02 when 10 V is input at
terminal A1.
Default: 100.0%
Min.: -999.9
Max.: 999.9
216
H3-04
(412)
Terminal A1 Bias Setting
Sets the level of the input value selected in H3-02 when 0 V is input at terminal
A1.
Default: 0.0%
Min.: -999.9
Max.: 999.9
216
H3-05
(413)
Terminal A3 Signal Level
Selection
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20 mA
3: 0 to 20 mA
Note: Use Jumper S1 to set input terminal
A3 for a current or voltage
input signal.
Default: 0
Range: 0 to 3
217
H3-06
(414)
Terminal A3 Function
Selection
Sets the function of terminal A3. Default: 2
Range: 0 to 32
217
H3-07
(415)
Terminal A3 Gain Setting
Sets the level of the input value selected in H3-06 when 10 V is input at
terminal A3.
Default: 100.0%
Min.: -999.9
Max.: 999.9
217
H3-08
(416)
Terminal A3 Bias Setting
Sets the level of the input value selected in H3-06 when 0 V is input at terminal
A3.
Default: 0.0%
Min.: -999.9
Max.: 999.9
217
H3-09
(417)
Terminal A2 Signal Level
Selection
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20 mA
3: 0 to 20 mA
Note: Use Jumper S1 to set input terminal
A2 for a current or voltage
input signal.
Default: 2
Range: 0 to 3
218
H3-10
(418)
Terminal A2 Function
Selection
Sets the function of terminal A2. Default: 0
Range: 0 to 32
218
H3-11
(419)
Terminal A2 Gain Setting
Sets the level of the input value selected in H3-10 when 10 V (20 mA) is input
at terminal A2.
Default: 100.0%
Min.: -999.9
Max.: 999.9
218
H3-12
(41A)
Terminal A2 Bias Setting
Sets the level of the input value selected in H3-10 when 0 V (0 or 4 mA) is
input at terminal A2.
Default: 0.0%
Min.: -999.9
Max.: 999.9
218
H3-13
(41B)
Analog Input Filter Time
Constant
Sets a primary delay filter time constant for terminals A1, A2, and A3. Used
for noise filtering.
Default: 0.03 s
Min.: 0.00
Max.: 2.00
218
H3-14
(41C)
Analog Input Terminal
Enable Selection
Determines which analog input terminals will be enabled when a digital input
programmed for “Analog input enable” (H1-oo = C) is activated.
1: Terminal A1 only
2: Terminal A2 only
3: Terminals A1 and A2 only
4: Terminal A3 only
5: Terminals A1 and A3
6: Terminals A2 and A3
7: All terminals enabled
Default: 7
Range: 1 to 7
218
H3-16
(2F0)
Terminal A1 Offset
Adds an offset when the analog signal to terminal A1 is at 0 V. Default: 0
Min.: -500
Max.: 500
219
B.7 H Parameters: Multi-Function Terminals
416
YASKAWA SIEP YAIP1U 01A AC Drive - P1000 Technical Manual