Yaskawa CIMR-PU2A0081 [92/548] Control i o connections

Превью страниц Страница 92 / 548
Yaskawa CIMR-PU2A0250 [92/548] Control i o connections
3.10 Control I/O Connections
u
Sinking/Sourcing Mode Switch for Digital Inputs
Use the wire jumper between terminals SC and SP or SC and SN to select between Sink mode, Source mode or external power
supply for the digital inputs S1 to S8 as shown in Table 3.11 (Default: Sink mode, internal power supply).
NOTICE: Do not short terminals SP and SN. Failure to comply will damage the drive.
Table 3.11 Digital Input Sink/Source/External Power Supply Selection
Mode
Drive Internal Power Supply
(Terminals SN and SP)
External 24 Vdc Power Supply
Sinking Mode (NPN)
SC
S8
S7
24 Vdc
SP
SN
SC
S8
S7
24 Vdc
SP
SN
External
24 Vdc
Sourcing Mode (PNP)
SC
S8
S7
24 Vdc
SP
SN
SC
S8
S7
24 Vdc
SP
SN
External
24 Vdc
u
Using the Pulse Train Output
The pulse train output terminal MP can supply power or be used with an external power supply.
NOTICE: Connect
peripheral devices in accordance with the specifications. Failure to comply may cause unexpected drive operation, and
can damage the drive or connected circuits.
n
Using Power from the Pulse Output Terminal (Source Mode)
The high voltage level of the pulse output terminal depends on the load impedance.
Load Impedance R
L
(kΩ) Output Voltage V
MP
(V) (insulated)
1.5 kΩ 5 V
4 kΩ 8 V
10 kΩ 10 V
Note:
The load resistance needed in order to get a certain high level voltage V
MP
can be calculated by: R
L
= V
MP
2 / (12 – V
MP
)
3.10 Control I/O Connections
92
YASKAWA SIEP YAIP1U 01A AC Drive - P1000 Technical Manual