Yaskawa CIMR-PU2A0312 [144/548] B2 dc injection braking and short circuit braking
Setting 0: Disabled
A Run command is not accepted while the digital operator is in Programming Mode.
Setting 1: Enabled
A Run command is accepted in any digital operator mode.
Setting 2: Prohibit programming during run
It is not possible to enter the Programming Mode as long as the drive output is active. The Programming Mode cannot be
displayed during Run.
n
b1-11: Drive Delay Time Setting
If a time is set to b1-11, the drive will delay executing a Run command until the set time has expired. During Drive Delay
Time execution, the digital operator keypad will display “WrUn”. Both Alarm and Run indicators will blink while the drive
waits to execute the Run command.
No. Parameter Name Setting Range Default
b1-11 Drive Delay Time Setting 0 to 600 s 0
n
b1-14: Phase Order Selection
Sets the phase order for drive output terminals U/T1, V/T2, and W/T3.
Switching motor phases will reverse the direction of the motor.
No. Parameter Name Setting Range Default
b1-14 Phase Order Selection 0, 1 0
n
b1-15: Frequency Reference Selection 2
Enabled when H1-oo = 2 and the
terminal is closed. Refer to Setting 2: External Reference 1/2 Selection on page 198 and
Refer to b1-02: Run Command Selection 1 on page 140 for details.
No. Parameter Name Setting Range Default
b1-15 Frequency Reference Selection 2 0 to 4 0
n
b1-16: Run Command Selection 2
Enabled when H1-oo = 2 and the
terminal is closed. Refer to Setting 2: External Reference 1/2 Selection on page 198 and
Refer to b1-01: Frequency Reference Selection 1 on page 139 for details.
No. Parameter Name Setting Range Default
b1-16 Run Command Selection 2 0 to 3 0
n
b1-17: Run Command at Power Up
Determines whether an external Run command that is active during power up will start the drive.
No. Parameter Name Setting Range Default
b1-17 Run Command at Power Up 0, 1
u
b2: DC Injection Braking and Short Circuit Braking
These parameters determine operation of the DC Injection Braking, Zero Speed Control, and Short Circuit Braking features.
n
b2-01: DC Injection Braking Start Frequency
Active when “Ramp to Stop” is selected as the stopping method (b1-03 = 0).
No. Name Setting Range Default
b2-01 DC Injection Braking Start Frequency 0.0 to 10.0 Hz 0.5
V/f Control
Sets the starting frequency for DC Injection Braking at Stop. When the output frequency falls below the setting of b2-01, DC
Injection Braking is enabled for the time set in parameter b2-04.
5.2 b: Application
144
YASKAWA SIEP YAIP1U 01A AC Drive - P1000 Technical Manual