Yaskawa CIMR-PU2A0211 [470/548] Selects the type of sequence used when the run command source is set to memobus modbus communications b1 02 b1 16 2
n
H5-11: Communications Enter Function Selection
Selects
whether an Enter command is necessary
to change parameter values via MEMOBUS/Modbus communications. Refer
to Enter Command on page 493.
No. Name Setting Range Default
H5-11 Communications Enter Function Selection 0 or 1 1
Setting 0: Enter command necessary
Parameter changes become effective after an Enter command. An Enter command must only be sent after the last parameter
change, not for each single parameter.
Setting 1: Enter command not necessary
Parameter value changes become effective immediately without the need to send an Enter command.
n
H5-12: Run Command Method Selection
Selects the type of sequence used when the Run command source is set to MEMOBUS/Modbus communications
(b1-02, b1-16 = 2).
No. Name Setting Range Default
H5-12 Run Command Method Selection 0 or 1 0
Setting 0: FWD/Stop, REV/Stop
Setting bit 0 of MEMOBUS/Modbus register 0001H will start and stop the drive in the forward direction. Setting bit 1 will
start and stop the drive in reverse.
Setting 1: Run/Stop, FWD/REV
Setting bit 0 of MEMOBUS/Modbus register 0001H will start and stop the drive. Setting bit 1 changes the direction.
C.4 MEMOBUS/Modbus Setup Parameters
470
YASKAWA SIEP YAIP1U 01A AC Drive - P1000 Technical Manual

Содержание

2656

Узнайте, как настроить параметры связи и команды управления в системах Modbus. Изменяйте значения параметров и управляйте устройствами эффективно.