Yaskawa CIMR-PU2A0081 — настройки частоты и пользовательские функции оператора [256/548]

Превью страниц Страница 256 / 548
Yaskawa CIMR-PU2A0211 [256/548] Determines whether the lo re key on the digital operator will be enabled for switching between local and remote
No. Name Setting Range Default
o1-10 User-Set Display Units Maximum Value 1 to 60000
Determined by
o1-03
n
o1-11: User-Set Display Units Decimal Display
Determines how many decimal points should be used to set and display the frequency reference.
No. Name Setting Range Default
o1-11 User-Set Display Units Decimal Display 0 to 3
Determined by
o1-03
Setting 0: No Decimal Point
Setting 1: One Decimal Point
Setting 2: Two Decimal Points
Setting 3: Three Decimal Points
n
o1-13: Frequency Reference and Frequency Related Monitor Custom Units 1
Sets the first character of the customer-specified unit display when o1-03 is set to 3 and o1-09 is set to 24.
No. Name Setting Range Default
o1-13
Frequency Reference and Frequency Related Monitor Custom Units
1
30 to 7A 41
n
o1-14: Frequency Reference and Frequency Related Monitor Custom Units 2
Sets the second character of the customer-specified unit display when o1-03 is set to 3 and o1-09 is set to 24.
No. Name Setting Range Default
o1-14
Frequency Reference and Frequency Related Monitor Custom Units
2
30 to 7A 41
n
o1-15: Frequency Reference and Frequency Related Monitor Custom Units 3
Sets the third character of the customer-specified unit display when o1-03 is set to 3 and o1-09 is set to 24.
No. Name Setting Range Default
o1-14
Frequency Reference and Frequency Related Monitor Custom Units
3
30 to 7A 41
u
o2: Digital Operator Keypad Functions
These parameters determine the functions assigned to the operator keys.
n
o2-01: LO/RE (LOCAL/REMOTE) Key Function Selection
Determines whether the LO/RE key on the digital operator will be enabled for switching between LOCAL and REMOTE.
No. Name Setting Range Default
o2-01 LO/RE Key Function Selection 0, 1 1
Setting 0: Disabled
The LO/RE key is disabled.
Setting 1: Enabled
The LO/RE switches between LOCAL and REMOTE operation. Switching is possible during stop only. When LOCAL is
selected, the LED indicator on the LO/RE key will light up.
WARNING! Sudden Movement Hazard. The drive may start unexpectedly if the Run command is already applied when switching from
LOCAL mode to REMOTE mode when b1-07 = 1, resulting in death or serious injury. Check all mechanical or electrical connections
thoroughly before making any setting changes to o2-01 and b1-07. Table 5.36 lists the setting combinations for o2-01 and b1-07.
5.10 o: Operator Related Settings
256
YASKAWA SIEP YAIP1U 01A AC Drive - P1000 Technical Manual
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Содержание

2656