Yaskawa CIMR-PU2A0081 — настройки DeviceNet для управления приводами: параметры и значения [194/548]

Превью страниц Страница 194 / 548
Yaskawa CIMR-PU2A0211 [194/548] F6 56 to f6 61 devicenet scaling factors
Settings:
F6-51 Communication Speed F6-51 Communication Speed
0 125 kbps 3 Adjustable from Network
1 250 kbps 4 Auto detection
2 500 kbps
n
F6-52: DeviceNet PCA Setting
Defines the format for data the drive receives from the DeviceNet master.
No. Parameter Name Setting Range Default
F6-52 DeviceNet PCA Setting 0 to 255 21
n
F6-53: DeviceNet PPA Setting
Defines the format for data sent from the drive to the DeviceNet master.
No. Parameter Name Setting Range Default
F6-53 DeviceNet PPA Setting 0 to 255 71
n
F6-54: DeviceNet Idle Mode Fault Detection
Determines
whether the drive triggers an EF0 fault
when no data is received from the master (e.g., when the master is idling).
No. Parameter Name Setting Range Default
F6-54 DeviceNet Idle Mode Fault Detection 0, 1 0
Setting 0: Enabled
Setting 1: Disabled, no fault detection
n
F6-55: DeviceNet Baud Rate Monitor
Displays the baud rate currently being used for network communications. F6-55 is used only as a monitor.
No. Parameter Name Setting Range Default
F6-55 DeviceNet Baud Rate Monitor 0 to 2 (read only) 0
Settings:
F6-55 Communication Speed F6-55 Communication Speed
0 125 kbps 2 500 kbps
1 250 kbps
n
F6-56 to F6-61: DeviceNet Scaling Factors
These parameters define scaling factors for drive monitors in the DeviceNet Class ID 2AH - AC/DC Drive Object.
No. Parameter Name Setting Range Default
F6-56 DeviceNet Speed Scaling -15 to 15 0
F6-57 DeviceNet Current Scaling -15 to 15 0
F6-58 DeviceNet Torque Scaling -15 to 15 0
F6-59 DeviceNet Power Scaling -15 to 15 0
F6-60 DeviceNet Voltage Scaling -15 to 15 0
F6-61 DeviceNet Time Scaling -15 to 15 0
Setting
The monitor value in the AC/DC Drive Object 2AH is calculated by:
AC/DC Drive Object 2AH Monitor = Drive Value × 2
Scaling
Example:
If the drive output frequency monitor (U1-02) is 5.00 and the scaling is set to F6-56 = 6, then the value in the AC/DC Drive
Object 2AH, Instance 1, Attribute 7 would be 500 × 2
6
= 32000.
5.6 F: Option Settings
194
YASKAWA SIEP YAIP1U 01A AC Drive - P1000 Technical Manual

Содержание

2656

Изучите настройки DeviceNet для управления приводами, включая скорость связи, параметры PCA и PPA, а также режимы обнаружения ошибок и масштабирования.