B.10 o: Operator-Related Settings
The o parameters set up the digital operator displays.
u
o1: Digital Operator Display Selection
No.
(Addr.
Hex)
Name Description Values Page
o1-01
(500)
Drive Mode Unit Monitor
Selection
Selects the content of the last monitor that is shown when scrolling through
Drive Mode display. Enter the last three digits of the monitor parameter
number to be displayed: Uo-oo.
Default: 106
(Monitor U1-06)
Range: 104 to 809
254
o1-02
(501)
User Monitor Selection after
Power Up
1: Frequency reference (U1-01)
2: Direction
3: Output frequency (U1-02)
4: Output current (U1-03)
5: User-selected monitor (set by o1-01)
Default: 1
Range: 1 to 5
254
o1-03
(502)
Digital Operator Display
Selection
Sets the units the drive should use to display the frequency reference and motor
speed monitors.
0: 0.01 Hz
1: 0.01% (100% = E1-04)
2: r/min (calculated using the number of motor poles setting in E2-04)
3: User-selected units (set by o1-09, o1-10 and o1-11)
Default: 0
Range: 0 to 3
254
o1-06
(517)
User Monitor Selection
Mode
Monitor Mode Sel
Selects the monitors displayed on the second and third lines of the digital
operator display.
0: 3 Monitor Sequential (displays the next two sequential monitors)
0: 3 Mon
Sequential
1: 3 Monitor Selectable
1: 3 Mon Selectable
(set by o1-07 and o1-08)
Default: 0
Range: 0, 1
254
o1-07
(518)
Second Line Monitor
Selection
2nd Monitor Sel
Selects the monitor that is shown in the second line.
Enter the last three digits of the monitor parameter number to be displayed:
Uo-oo. For example, set "403" to display monitor parameter U4-03.
Note: Parameter is effective only when o1-06 is set to 1.
Default: 102
Range: 101 to 799
254
o1-08
(519)
Third Line Monitor
Selection
3rd Monitor Sel
Selects the monitor that is shown in the third line.
Enter the last three digits of the monitor parameter number to be displayed:
Uo-oo. For example, set "403" to display monitor parameter U4-03.
Note: Parameter is effective only when o1-06 is set to 1.
Default: 103
Range: 101 to 799
254
o1-09
(51C)
Frequency Reference
Display Units
Fref Disp Unit
Sets unit display for the frequency reference parameters and frequency related
monitors when o1-03 = 3.
0: WC
0: WC
(Inch of water)
1: PSI
1: PSI
(Pounds per square inch)
2: GPM
2: GPM
(Gallons per minute)
3: F
3: °F
(Degrees Fahrenheit)
4: CFM
4: CFM
(Cubic feet per minute)
5: CMH
5: CMH
(Cubic meters per hour)
6: LPH
6: LPH
(Liters per hour)
7: LPS
7: LPS
(Liters per second)
8: Bar
8: Bar
(Bar)
9: Pa
9: Pa
(Pascal)
10: C
10: °C
(Degrees Celsius)
11: Mtr
11: Mtr
(Meters)
12: Ft
12: Ft
(Feet)
13: LPM
13: LPM
(Liters per minute)
14: CMM
14: CMM
(Cubic meters per minute)
15: “Hg
15: Hg
(inches of mercury)
24: Custom units (determined by o1-13 to o1-15)
25: None
25: No Unit
Default: 25
Range: 0 to 15; 24,
25
254
o1-10
(520)
User-Set Display Units
Maximum Value
These settings define the display values when o1-03 is set to 3.
o1-10 sets the display value that is equal to the maximum output frequency.
o1-11 sets the position of the decimal position.
Default:
<1>
Range: 1 to 60000
255
o1-11
(521)
User-Set Display Units
Decimal Display
Default:
<1>
Range: 0 to 3
256
o1-13
(3105)
Frequency Reference and
Frequency Related Monitor
Custom Units 1
Fref Cust Unit 1
Sets the first character of the customer-specified unit display when o1-03 is
set to 3 and o1-09 is set to 24.
Default: 41
Range: 30 to 7A
256
B.10 o: Operator-Related Settings
428