Yaskawa CIMR-PU2A0081 [259/548] O4 01 cumulative operation time setting
Setting 0: Disabled
Setting 1: Enabled
u
o3: Copy Function
These parameters control the Copy function of the digital operator. The Copy function stores parameter settings into the
memory of the digital operator to facilitate the transfer of those settings to other drives that are the same model, capacity, and
same control mode setting. Refer to Copy Function Related Displays on page 310 for a description of errors and displays.
n
o3-01: Copy Function Selection
Instructs the drive to Read, Write, or Verify parameter settings.
No. Name Setting Range Default
o3-01 Copy Function Selection 0 to 3 0
Setting 0: Copy Select (no function)
Setting 1: INV --> OP READ
Copies all parameters from the drive to the digital operator.
Note: The copy protection for the digital operator is enabled by default. Set o3-01 to 1 to unlock copy protection.
Setting 2: OP --> INV WRITE
Copies all parameters from the digital operator to the drive.
Setting 3: OP<-->INV VERIFY
Compares the parameters in the drive with the parameter settings saved on the digital operator for matches.
n
o3-02: Copy Allowed Selection
Allows and restricts the use of the Copy function.
No. Name Setting Range Default
o3-02 Copy Allowed Selection 0, 1 0
Setting 0: Disabled
Setting 1: Enabled
u
o4: Maintenance Monitor Settings
n
o4-01: Cumulative Operation Time Setting
Sets the cumulative operation time of the drive. The user can also manually set this parameter to begin keeping track of
operation time from some desired value. Total operation time can be viewed in monitor U4-01.
Note: The
value in o4-01 is set in 10 h units. For example, a setting of 30 will set the cumulative operation time counter to 300 h. 300 h will also
be displayed in monitor U4-01.
No. Name Setting Range Default
o4-01 Cumulative Operation Time Setting 0 to 9999 0
n
o4-02: Cumulative Operation Time Selection
Selects
the conditions for how the drive
keeps track of its total operation time. This time log can be viewed in monitor U4-01.
No. Name Setting Range Default
o4-02 Cumulative Operation Time Selection 0, 1 0
Setting 0: Power on time
The drive logs the time it is connected to a power supply, regardless of whether the motor is running.
Setting 1: Run time
The drive logs the time that the output is active including when the Run command is active (even if the motor is not rotating)
and when there is voltage output.
5.10 o: Operator Related Settings
YASKAWA SIEP YAIP1U 01A AC Drive - P1000 Technical Manual
259
5
Parameter Details