Yaskawa CIMR-PU2A0211 [407/548] Parameters f6 01 through f6 03 and f6 06 through f6 08 are used for cc link canopen devicenet profibus dp and mechatrolink ii options other parameters in the f6 group are used for communication protocol specific settings f7 parameters are used for ethernet ip modbus tcp ip and profinet options
No.
(Addr.
Hex)
Name Description Values Page
F4-08
(398)
Terminal V2 Signal Level
0: 0 to 10 V
1: -10 to 10 V
Default: 0
Range: 0, 1
189
u
F6, F7: Communication Option Card
Parameters F6-01 through F6-03 and F6-06 through F6-08 are used for CC-Link, CANopen, DeviceNet, PROFIBUS-DP, and
MECHATROLINK-II options. Other parameters in the F6 group are used for communication-protocol-specific settings. F7
parameters are used for EtherNet/IP, Modbus TCP/IP, and PROFINET options.
No.
(Addr.
Hex)
Name Description Values Page
F6-01
(3A2)
Communications Error
Operation Selection
0: Ramp to stop. Decelerate to stop using the deceleration time in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration time in C1-09.
3: Alarm only.
Default: 1
Range: 0 to 3
190
F6-02
(3A3)
External Fault from Comm.
Option Detection Selection
0: Always detected.
1: Detection during run only.
Default: 0
Range: 0, 1
190
F6-03
(3A4)
External Fault from Comm.
Option Operation Selection
0: Ramp to stop. Decelerate to stop using the deceleration time in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration time in C1-09.
3: Alarm only.
Default: 1
Range: 0 to 3
190
F6-04
(3A5)
bUS Error Detection Time
Sets the delay time for error detection if a bus error occurs. Default: 2.0 s
Min.: 0.0
Max.: 5.0
191
F6-07
(3A8)
Multi-Step Speed Enable/
Disable Selection when
NefRef/ComRef is Selected
0: Multi-step reference disabled (same as F7)
1: Multi-step reference enabled (same as V7)
Default: 0
Range: 0, 1
190
F6-08
(36A)
<1>
Reset Communication
Parameters
0: Communication-related parameters (F6-oo) are not reset when the drive
is initialized using A1-03.
1: Reset all communication-related parameters (F6-oo) when the drive is
initialized using A1-03.
Default: 0
Range: 0, 1
191
F6-10
(3B6)
CC-Link Node Address
Sets the node address if a CC-Link option is installed. Default: 0
Min.: 0
Max.: 64
191
F6-11
(3B7)
CC-Link Communication
Speed
0: 156 Kbps
1: 625 Kbps
2: 2.5 Mbps
3: 5 Mbps
4: 10 Mbps
Default: 0
Range: 0 to 4
191
F6-14
(3BB)
CC-Link bUS Error Auto
Reset
0: Disabled
1: Enabled
Default: 0
Range: 0, 1
191
F6-20
(36B)
MECHATROLINK Station
Address
Sets the station address when the MECHATROLINK-II option has been
installed.
Default: 21
Min.: 20
Max.: 3F
F6-21
(36C)
MECHATROLINK Frame
Size
0: 32 byte
1: 17 byte
Default: 0
Range: 0, 1
F6-22
(36D)
MECHATROLINK Link
Speed
0: 10 Mbps
1: 4 Mbps
Default: 0
Range: 0, 1
F6-23
(36E)
MECHATROLINK
Monitor Selection (E)
Sets the MECHATROLINK-II monitor (E). Default: 0
Min.: 0
Max.: FFFF
F6-24
(36F)
MECHATROLINK
Monitor Selection (F)
Sets the MECHATROLINK-II monitor (F). Default: 0
Min.: 0
Max.: FFFF
F6-25
(3C9)
Operation Selection at
Watchdog Timer Error (E5)
0: Ramp to stop. Decelerate using the deceleration time in C1-02.
1: Coast to stop
2: Fast stop. Decelerate using the deceleration time in C1-09.
3: Alarm only
Default: 1
Range: 0 to 3
F6-26
(3CA)
MECHATROLINK bUS
Errors Detected
Sets the number of option communication errors (bUS). Default: 2
Min.: 2
Max.: 10
B.6 E: Motor Parameters
YASKAWA SIEP YAIP1U 01A AC Drive - P1000 Technical Manual
407
B
Parameter List