Yaskawa CIMR-PU2A0081 [514/548] Closed loop crimp terminal recommendations

Превью страниц Страница 514 / 548
Yaskawa CIMR-PU2A0081 [514/548] Closed loop crimp terminal recommendations
Drive Model Terminal
Recomm. Gauge
AWG, kcmil
Wire Range
AWG, kcmil
Screw
Size
Tightening Torque
N·m (lb.in.)
5A0077
R/L1, S/L2, T/L3 3 10 to 4/0
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3 3 10 to 4/0
–, +1 3 to 4/0
+3 6 to 4/0
4 4
5A0099
R/L1, S/L2, T/L3 1/0 10 to 4/0
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3 1 10 to 4/0
–, +1 2 to 4/0
+3 4 to 4/0
4 4
5A0125
R/L1, S/L2, T/L3 2/0 1 to 300
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3 2/0 1 to 300
–, +1 2/0 to 3/0
+3 1 to 1/0
3 4 to 300
5A0145
R/L1, S/L2, T/L3 3/0 2/0 to 300
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3 3/0 2/0 to 300
–, +1 3/0 to 4/0
+3 1/0 to 2/0
3 4 to 300
5A0192
R/L1, S/L2, T/L3 300 2/0 to 600
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 250 2/0 to 600
–, +1 2/0 to 400
+3 2/0 to 250 M10
18 to 23
(159 to 204)
1 1 to 350 M12
32 to 40
(283 to 354)
5A0242
R/L1, S/L2, T/L3 400 2/0 to 600
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 350 2/0 to 600
–, +1 2/0 to 500
+3 250 to 300 M10
18 to 23
(159 to 204)
1 1 to 350 M12
32 to 40
(283 to 354)
Closed-Loop Crimp Terminal Recommendations
Yaskawa recommends crimp terminals made by JST
and Tokyo DIP (or equivalent) for the insulation cap. Table D.7 matches
the wire gauges and terminal screw sizes with Yaskawa-recommended crimp terminals, tools, and insulation caps. Refer to
the appropriate Wire Gauge and Torque Specifications table for the wire gauge and screw size for your drive model. Place
orders with a Yaskawa representative or the Yaskawa sales department.
The closed-loop crimp terminal sizes and values listed in Table D.7 are Yaskawa recommendations.
Wire gauge values shown in bold italic are the recommended values. Refer to local codes for proper selections.
Table D.7 Closed-Loop Crimp Terminal Size
Drive Model
Wire Gauge (AWG, kcmil)
Screw
Size
Crimp
Terminal
Model
Number
Tool
Insulation
Cap Model
No.
Code
<1>
R/L1, S/L2, T/L3 U/T1, V/T2, W/T3 Machine No. Die Jaw
200 V Class
2A0004
2A0006
2A0008
2A0010
14
M4
R2-4
YA-4 AD-900
TP-003 100-054-028
12
R5.5-4 TP-005 100-054-029
10
D.3 UL and CSA Standards
514
YASKAWA SIEP YAIP1U 01A AC Drive - P1000 Technical Manual

Содержание

2656