Yaskawa CIMR-PU2A0081 — настройки и характеристики моделей приводов для двигателей [456/548]

Превью страниц Страница 456 / 548
Yaskawa CIMR-PU2A0211 [456/548] Yaskawa siep yaip1u 01a ac drive p1000 technical manual
No. Name Unit Default Settings
Model CIMR-Po
4A0362 4A0414 4A0515 4A0675
o2-04 Drive Model Selection Hex. A9 AA AC AE
E2-11 Motor rated power kW (HP)
185
(300)
220
(350)
250
(400
-450)
355
(500
-550)
b3-04 V/f Gain during Speed Search % 60 60 60 60
b3-06 Output Current 1 during Speed Search 0.7 0.7 0.7 0.7
b3-07
Output Current 2 during Speed Search
(Speed Estimation Type)
b3-26 Start Speed Search Select
b8-03 Energy Saving Control Filter Time Constant s 2.00 2.00 2.00 2.00
b8-04 Energy Saving Coefficient Value 30.57 27.13 21.76 23.84
C5-17 Motor Inertia
kgm
2
3.60 4.10 6.50 12.00
C6-02 Carrier Frequency Selection 7 7 7 7
E2-01 Motor Rated Current A 310 370 500 650
E2-02 Motor Rated Slip Hz 1.3 1.3 1.25 1
E2-03 Motor No-Load Current A 81 96 130 130
E2-05 Motor Line-to-Line Resistance Ω 0.025 0.02 0.014 0.012
E2-06 Motor Leakage Inductance % 20 20 20 20
E2-10 Motor Iron Loss for Torque Compensation W 3200 3700 4700 5560
L2-02 Momentary Power Loss Ride-Thru Time s 2 2 2 2
L2-03 Momentary Power Loss Min. Basebl. Time s 1.9 2 2.1 2.3
L2-04 Momentary Power Loss Volt. Recov. Time s 1 1 1 1
L3-24 Motor Acceleration Time for Inertia Calculations s 0.864 0.91 1.392 1.667
L8-02 Overheat Alarm Level °C 130 140 140 140
L8-35 Installation Method Selection 0 0 0 0
L8-38 Carrier Frequency Reduction Selection 2 2 2 2
n1-03 Hunting Prevention Time Constant ms 30 100 100 100
B.15 Defaults by Drive Model