Refer to L4-01, L4-02: Speed Agreement Detection Level and Detection Width on page 241 for more instructions.
Setting 4: Frequency Detection 1
The output opens when the output frequency rises
above the detection level set in L4-01 plus the detection width set in L4-02.
The terminal remains open until the output frequency or motor speed fall below the level set in L4-01.
Status Description
Open Output frequency or motor speed exceeded L4-01 + L4-02.
Closed Output frequency or motor speed is below L4-01 or has not exceeded L4-01 + L4-02.
Note: Frequency detection works in forward and reverse. The value of L4-01 is used as the detection level for both directions.
L4-02
Frequency
detection 1
ON
OFF
L4-02
L4-01
L4-01
Output Frequency
or Motor Speed
Figure 5.49 Frequency Detection 1 Time Chart
Refer to L4-01, L4-02: Speed Agreement Detection Level and Detection Width on page 241 for more details.
Setting 5: Frequency Detection 2
The output closes when the output frequency is above the detection level set in L4-01. The terminal remains closed until the
output frequency or motor speed fall below L4-01 minus the setting of L4-02.
Status Description
Open Output frequency or motor speed is below L4-01 minus L4-02 or has not exceeded L4-01.
Closed Output frequency or motor speed exceeded L4-01.
Note: Frequency detection works in forward and reverse. The value of L4-01 is used as the detection level for both directions.
L4-02
Frequency
Detection 2
ON
OFF
L4-02
L4-01
L4-01
Output Frequency
or Motor Speed
Figure 5.50 Frequency Detection 2 Time Chart
Refer to L4-01, L4-02: Speed Agreement Detection Level and Detection Width on page 241 for more details.
Setting 6: Drive Ready
The
output closes when the drive is ready
to operate the motor. The terminal will not close under the conditions listed below,
and any Run commands will be disregarded.
When the power is shut off
During a fault
When the internal power supply of the drive has malfunctioned
When a parameter setting error makes it impossible to run
Although stopped, an overvoltage or undervoltage situation occurs
5.7 H: Terminal Functions
YASKAWA SIEP YAIP1U 01A AC Drive - P1000 Technical Manual
209
5
Parameter Details