Table 3.13 Voltage/Current Selection Parameter Details
No. Parameter Name Description
Setting
Range
Default
Setting
H3-01 Terminal A1 signal level selection
Selects the signal level for terminal A1.
0: 0 to 10 Vdc
1: -10 to 10 Vdc
2: 4 to 20 mA
3: 0 to 20 mA
0 to 3 0
H3-05 Terminal A3 signal level selection
Selects the signal level for terminal A3.
0: 0 to 10 Vdc
1: -10 to 10 Vdc
2: 4 to 20 mA
3: 0 to 20 mA
0 to 3 2
H3-09 Terminal A2 signal level selection
Selects the signal level for terminal A2.
0: 0 to 10 Vdc
1: -10 to 10 Vdc
2: 4 to 20 mA
3: 0 to 20 mA
0 to 3 0
u
Terminal AM/FM Signal Selection
The signal type for terminals AM and FM can be set to either voltage or current output using jumper S5 on the terminal board
as explained in Table 3.14. When changing the setting of jumper S5, parameters H4-07 and H4-08 must be set accordingly.
The default selection is voltage output for both terminals. Refer to Switches and Jumpers on the Terminal Board on page
91 for locating jumper S5.
Table 3.14 Jumper S5 Settings
Terminal Voltage Output Current Output
Terminal AM
AMFM
V
I
AMFM
V
I
Terminal FM
AMFM
V
I
AMFM
V
I
Table 3.15 Parameter H4-07 and H4-08 Details
No. Parameter Name Description
Setting
Range
Default
Setting
H4-07 Terminal AM signal level selection 0: 0 to 10 Vdc
1: -10 to 10 Vdc
2: 4 to 20 mA
0 to 2 0
H4-08 Terminal FM signal level selection
u
MEMOBUS/Modbus Termination
This drive is equipped with a built-in
termination resistor for the RS-422/485 communication port. DIP switch S2 enables or
disabled the termination resistor as shown in Table 3.16. The OFF position is the default. The termination resistor should be
placed to the ON position when the drive is the last in a series of slave drives. Refer to Switches and Jumpers on the Terminal
Board on page 91 to locate switch S2.
Table 3.16 MEMOBUS/Modbus Switch Settings
S2 Position Description
ON Internal termination resistor ON
OFF Internal termination resistor OFF (default setting)
Note: Refer to MEMOBUS/Modbus Communications on page 463 for details on MEMOBUS/Modbus.
3.10 Control I/O Connections
94
YASKAWA SIEP YAIP1U 01A AC Drive - P1000 Technical Manual