Yaskawa CIMR-PU2A0081 [196/548] H1 multi function digital inputs

Превью страниц Страница 196 / 548
Yaskawa CIMR-PU2A0211 [196/548] H1 multi function digital inputs
5.7 H: Terminal Functions
H parameters assign functions to the external terminals.
u
H1: Multi-Function Digital Inputs
n
H1-01 to H1-08: Functions for Terminals S1 to S8
These parameters assign functions to the multi-function digital inputs. The various functions and settings are listed in Table
5.29.
No. Parameter Name
Setting
Range
Default
H1-01 Multi-Function Digital Input Terminal S1 Function Selection 1 to 9F
40 (F)
<1>
: Forward Run Command (2-Wire sequence)
H1-02 Multi-Function Digital Input Terminal S2 Function Selection 1 to 9F
41 (F)
<1>
: Reverse Run Command (2-Wire sequence)
H1-03 Multi-Function Digital Input Terminal S3 Function Selection 0 to 9F 24: External Fault
H1-04 Multi-Function Digital Input Terminal S4 Function Selection 0 to 9F 14: Fault Reset
H1-05 Multi-Function Digital Input Terminal S5 Function Selection 0 to 9F
3 (0)
<1>
: Multi-Step Speed Reference 1
H1-06 Multi-Function Digital Input Terminal S6 Function Selection 0 to 9F
4 (3)
<1>
: Multi-Step Speed Reference 2
H1-07 Multi-Function Digital Input Terminal S7 Function Selection 0 to 9F
6 (4)
<1>
: Jog Reference Selection
H1-08 Multi-Function Digital Input Terminal S8 Function Selection 0 to 9F
8: (6)
<1>
: External Baseblock Command
<1> Number appearing in parenthesis is the default value after performing a 3-Wire initialization (A1-03 = 3330).
Table 5.29 Multi-Function Digital Input Terminal Settings
Setting Function Page
0 3-Wire Sequence 197
1 LOCAL/REMOTE Selection 197
2 External Reference 1/2 Selection 198
3 Multi-Step Speed Reference 1
1984 Multi-Step Speed Reference 2
5 Multi-Step Speed Reference 3
6 Jog reference Selection 198
7 Accel/Decel Time Selection 1 198
8 Baseblock Command (N.O.)
198
9 Baseblock Command (N.C.)
A Accel/Decel Ramp Hold 198
B Drive Overheat Alarm (oH2) 199
C Analog Terminal Input Selection 199
F Through Mode 199
10 Up Command
199
11 Down Command
12 Forward Jog
200
13 Reverse Jog
14 Fault Reset 200
15 Fast Stop (N.O.) 200
17 Fast Stop (N.C.) 200
18 Timer Function Input 201
19 PID Disable 201
1A Accel/Decel Time Selection 2 201
1B Program Lockout 201
1E Reference Sample Hold 201
20 to 2F External Fault 202
30 PID Integral Reset 202
31 PID Integral Hold 202
Setting Function Page
32 Multi-Step Speed Reference 4 202
34 PID Soft Starter Cancel 202
35 PID Input Level Selection 202
40 Forward Run Command (2-Wire sequence)
203
41 Reverse Run Command (2-Wire sequence)
42 Run Command (2-Wire sequence 2)
203
43 FWD/REV Command (2-Wire sequence 2)
47 Node Setup 203
51 Disable Sequence Timers 203
52 Cancel Active Sequence Timer 203
60 DC Injection Braking Command 203
61 External Speed Search Command 1 204
62 External Speed Search Command 2 204
63 Field Weakening 204
65 KEB Ride-Thru 1 (N.C.)
204
66 KEB Ride-Thru 1 (N.O.)
67 Communications Test Mode 204
68 High Slip Braking (HSB) 204
6A Drive Enabled 204
75 Up 2 Command
204
76 Down 2 Command
7A KEB Ride-Thru 2 (N.C.)
205
7B KEB Ride-Thru 2 (N.O.)
A8 Secondary PI Disable (N.O.) 206
A9 Secondary PI Disable (N.C.) 206
AA Secondary PI Inverse Operation 206
AB Secondary PI Integral Reset 206
AC Secondary PI Integral Hold 206
AD Select Secondary PI Parameters 206
5.7 H: Terminal Functions
196
YASKAWA SIEP YAIP1U 01A AC Drive - P1000 Technical Manual

Содержание

2656