Yaskawa CIMR-PU2A0211 [167/548] Sets the voltage limit for the speed search optimal output voltage detection as a percentage of the maximum output voltage the drive will keep the output voltage above this level during the search operation to prevent motor stalling
Reducing this setting increases the response time. If the filter time is too short, the motor may become unstable with a lighter
load.
No. Name Setting Range Default
b8-05 Power Detection Filter Time 0 to 2000 ms 20 ms
n
b8-06: Search Operation Voltage Limit
Sets the voltage limit for the Speed Search optimal output voltage detection as a percentage of the maximum output voltage.
The drive will keep the output voltage above this level during the search operation to prevent motor stalling.
No. Name Setting Range Default
b8-06 Search Operation Voltage Limit 0 to 100% 0%