Setting Function
4 Frequency Detection 1 209
5 Frequency Detection 2 209
6 Drive Ready 209
7 DC Bus Undervoltage 210
8 During Baseblock (N.O.) 210
9 Frequency Reference Source 210
A Run Command Source 210
B Torque Detection 1 (N.O.) 210
C Frequency Reference Loss 210
D Braking Resistor Fault 210
E Fault 210
F Through Mode 211
10 Minor Fault 211
11 Fault Reset Command Active 211
12 Timer Output 211
13 Speed Agree 2 211
14 User-Set Speed Agree 2 211
15 Frequency Detection 3 212
16 Frequency Detection 4 212
17 Torque Detection 1 (N.C.)
210
18 Torque Detection 2 (N.O.)
19 Torque Detection 2 (N.C.) 210
1A During Reverse 213
1B During Baseblock (N.C.) 213
1E Restart Enabled 213
1F Motor Overload Alarm (oL1) 213
Setting Function
20 Drive Overheat Pre-Alarm (oH) 213
22 Mechanical Weakening Detection 214
2F Maintenance Period 214
37 During Frequency Output 214
38 Drive Enabled 214
39 Watt Hour Pulse Output 214
3C LOCAL/REMOTE Status 214
3D During Speed Search 214
3E PID Feedback Low 214
3F PID Feedback High 214
4A During KEB Operation 214
4C During Fast Stop 214
4D oH Pre-Alarm Time Limit 215
4E
<2>
Braking Transistor Fault (rr) 215
4F
<2>
Braking Resistor Overheat (rH) 215
50 Waiting to Run 215
51 Sequence timer 1 215
52 Sequence timer 2 215
53 Sequence timer 3 215
54 Sequence timer 4 215
58 UL6 Detected 215
60 Internal Cooling Fan Alarm 215
71 Secondary PI Feedback Low 215
72 Secondary PI Feedback High 215
100 to 192 Functions 0 to 92 with Inverse Output 215
<2> Not available in models 2A0169 to 2A0415 and 4A0088 to 4A0675.
Setting 0: During Run
Output closes when the drive is outputting a voltage.
Status Description
Open Drive is stopped.
Closed A Run command is input or the drive is in deceleration or DC injection.
ON
ON
OFF
OFF
ONOFF
Run command
Baseblock
command
Output
frequency
During Run
Figure 5.45 During Run Time Chart
Setting 1: Zero Speed
Terminal closes when the output frequency falls below the minimum output frequency set to E1-09 or b2-01.
Status Description
Open Output frequency is above the minimum output frequency set to E1-09 or b2-01
Closed Output frequency is less than the minimum output frequency set to E1-09 or b2-01
5.7 H: Terminal Functions
YASKAWA SIEP YAIP1U 01A AC Drive - P1000 Technical Manual
207
5
Parameter Details